IMPORTANT:
If the Photo Catalytic section should become dirty, it may
be cleaned with compressed air only, no solvents should
be used. If the Photo Catalytic section becomes wet, allow
the section to air dry before reinstallation.

The mesh screens on the Photo catalytic chamber are
coated with a patented process known to chemically
breakdown VOC’s and Odors as well as reduce some
microbial populations on contact. This coating is clear in
color. Under normal operating conditions this chamber
should not require replacement within intervals of less than
five years.

The Air cleaner should never be run without the MERV-
11or HEPA Filter in place.

Using less than a MERV-11 Filter rating will reduce the
effectiveness of this product.

MERV or Minimum efficiency rating value is a number
assigned to filters indicating their ability to capture particles
and dust, the higher the number the better the filter. A
MERV 11 filter is 40% more effective than a MERV-8. Be
sure that a MERV-11 or a higher filter rating is requested
for replacements in this product.

General Dimensions and Features:


Maintenance:

The filter media in your air cleaner must be changed
periodically. The frequency of filter replacement is best
determined by visual examination. However, an annual
replacement of the filter is strongly recommended.
Replacement filters can be obtained through your
installing contractor or local dealer.

Steps for replacing filters:

1. Open the access door by removing grill.
2. Pull out used filter and discard.
3. Slide new filter into cabinet with “airflow label
pointing in the direction of the airflow.
4. Replace access grill.

Steps for replacing Germicidal UVC Lamps

:

1. Turn the systems power off.
2. Open the drop down access panel via the 2 half

turn access screws.

3. Locate the lamp assembly, and remove the lamp

connector. (See illustration on page 4)

4. Withdraw the UVC lamp assembly from their

mounting location.

5. Reverse the process with new lamps.

Be sure to recycle the used lamps in accordance with your
local codes for fluorescent lamps. If you are not sure on
how to recycle the lamps please call the Ultravation
customer service line at 866-468-8247.

New lamps should be cleaned with a damp cloth or with
rubbing alcohol to remove and finger prints and debris
prior to installation.

23.75"

CEILING LINE

UV LAMPS

VOC FILTER

HINGED ACCESS PANEL

POWER SUPPLY INLET

47.75"

FILTER ACCESS PANEL

SUSPENSION EYEBOLTS