Warning, Danger – Electrolux EN18WI30LS User Manual

Page 20

Advertising
background image

18

Vertical Vent Termination- PVC/CPVC Materials Only

Firestop

Firestop/Support

Roof

Flashing

Storm

Collar

Hanger

Strap

Horizontal Vent Termination- PVC/CPVC Materials Only

Hanger

Straps

**1' (0.3m) Minimum

Slope vent

Upwards

**1' (0.3m) Minimum

* Not supplied with water
heater, order separately.

recommended, but not required.

Insert Bird
Screen* in
Each End
of Tee

Support

Insert Bird
Screen* in
End of 90
Elbow

Slope vent
Upwards

* Not supplied with water
heater, order separately.

**1' (0.3m)
Minimum

**1' (0.3m) minimum

recommended, but not required.

Exhaust

Intake

Exhaust

Intake

90 Elbow

SV Conversion Kit
Accessory
(#SV-CK-3)

90 Elbow

SV Conversion Kit
Accessory
(#SV-CK-3)

Inlet screen

Inlet screen

3” Min.

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

A tee, 90° elbow, or the TWHHORHOOD termination may be
used for the vent termination. It is not necessary to use bird
screens with the TWHHORHOOD termination.

Terminate at least 12" (300mm) above grade or above snow line.

Terminate at least 7' (2.1m) above a public walkway, 6' (1.8m) from
the combustion air intake of any appliance, and 3' (0.9m) from
any other building opening, gas utility meter, service regulator etc.

Terminate at least 3' (0.9m) above any forced air inlet within
10' (3m) , 4' (1.2m) below, 4' (1.2m) horizontally from or
1' (0.3m) above any door, window, or gravity air inlet into any
building per National Fuel Gas Code ANSI Z223.1/NFPA 54.

Slope the horizontal vent 1/4" upwards for every 12" (300mm)
toward the termination.

Use a condensation drain if necessary.

In the Commonwealth of Massachusetts a carbon monoxide detector
is required for all side wall horizontally vented gas fuel equipment.
Please refer to Technical Bulletin TB 010606 for full installation
instructions.

The TWHVERTCAP termination may be used
in place of elbows as the vertical vent termination.

Terminate at least 6' (1.8m) from the combustion air
intake of any appliance, and 3' (0.9m) from any other
building opening, gas utility meter, service regulator etc.

Enclose exterior vent systems below the roof line to limit
condensation and protect against mechanical failure.

When the vent penetrates a floor or ceiling and is not
running in a fire rated shaft, a firestop and support is
required.

When the vent termination is located not less than
8' (2.4m) from a vertical wall or similar obstruction,
terminate above the roof at least 2' (0.6m), but not
more than 6' (1.87m), in accordance with the National
Fuel Gas Code ANSI Z223.1/NFPA 54.

Provide vertical support every 3' (0.9m) or as required
by the vent pipe manufacturer's instructions.

A short horizontal section is recommended to prevent
debris from falling into the water heater.

When using a horizontal section, slope the horizontal
vent 1/4” upwards for every 12” (300mm) toward the
termination to drain condensate.

* Dip switch No.3 is turned on.

Vent Pipe Installation (When supplying combustion air from the indoors (SV, non-direct vent))

t%JTDPOOFDUQPXFSBOEUVSO0/EJQTXJUDIJGDPNCVTUJPOBJSXJMMCFTVQQMJFEGSPNUIF

indoors as illustrated to the right. Refer to page 31 for the location of the dip switch bank.

tSV Conversion kit #SV-CK-3 is required for the air intake. The SV Conversion Kit

#SV-CK-3 is contained within both the Horizontal Installation Kit (TWHHORKIT)
and the Vertical Installation Kit (TWHVERTKIT).

'BJMVSFUPQFSGPSNUIFBCPWFTUFQTDPVMESFTVMUJOBàSFPSFYQMPTJPODBVTJOH
property damage, personal injury or death.

3FGFSUPUIFJOTUSVDUJPOTQSPWJEFEXJUIUIFDPOWFSTJPOLJUGPSBEEJUJPOBMEFUBJMT

WARNING

When installing this water heater in an area with a large amount of lint such as a commercial Laundromat,
direct-vent ("-DV") system must be used. The "-SV" configuration (using an SV conversion kit) is prohibited.

DANGER

Advertising
This manual is related to the following products: