Venting the Pellet Stove

•

INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER).

•

DO NOT CONNECT THE PELLET VENT TO A VENT SERVING ANY OTHER
APPLIANCE OR STOVE.

•

DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF
THIS UNIT.

• USE AN APPROVED WALL THIMBLE WHEN PASSING THE VENT THROUGH

WALLS AND A CEILING SUPPORT/FIRE STOP SPACER WHEN PASSING THE
VENT THROUGH CEILINGS (MAKE SURE TO MAINTAIN CLEARANCE TO ANY
C O M B U S T I B L E S .

Maximum Venting Distance:

•

Maximum venting height is 33' (maximum horizontal offset is 10')

•

Use no more than 180

°

of elbows (two 90

°

elbows, or two 45

°

& one 90

°

elbow, etc.).

Pellet Vent Type

•

Must be Type "L" vent and/or Type "L" chimney liner.

•

Use 4" diameter vent.

Installing the Pellet Vent

•

Pellet vent connections must be sealed
airtight with 500

°

F. RTV silicone and

screwed together with at least three
sheet metal screws.

Seal each vent section (including
adapters, elbows, etc...) by
injecting a liberal amount of 500°
F. RTV silicone into the gap
between sections.

500

° F. RTV

Silicone

The exhaust quick-

connect can be

removed to allow for

installation and

cleaning.

Pellet Vent Termination

•

Termination must be a minimum 6" above the top of the chimney (NOTE: the chimney must meet
local codes for height above the roof or other obstructions).

•

Must have an approved cap (to prevent water from entering).

•

Must not be located where it will become plugged by snow or other material.