Why do i need a fire rated exhaust fan, What is a fire rated exhaust fan, What does a fire rated exhaust fan do – Air King FRAS120 User Manual

Page 2: Deluxe quiet fire rated exhaust fan series, Advantage 4" duct fire rated exhaust fan series, Cu s

Advertising
background image

What is a Fire Rated

Exhaust Fan?

The Air King Fire Rated Exhaust Fan Series consists

of a three part system designed to meet the NFP

A

’s

(National Fire Protection Association) Standard 90A.

The unit consists of a Housing, a Ceiling Radiation

Damper that is ULC Classified and rated for 3 - 4 hour

fire resistance, and the Motor/Blade/Grill. When all

three of these parts are used together they create a

Fire Rated Exhaust Fan.

What does a Fire

Rated Exhaust Fan Do?

The Fire Rated Exhaust Fan Series is designed to

automatically shut off and seal the duct from the rest

of the dwelling once the temperature of air passing

through the damper exceeds that of the fusible link.

This prevents the spread of smoke or fire through the

ducting system to the other rooms or dwellings.

Why do I need a Fire

Rated Exhaust Fan?

Your local code will dictate if and what type of Fire

Rated Exhaust Fan you will need. Generally any time

a common duct is used in a multi-dwelling situation,

a Fire Rated Exhaust Fan will be required to prevent

fire from using the common ducting to spread from

one dwelling to the next. This is usually true in

commercial and multi-family housing constructions.

Deluxe Quiet Fire

Rated Exhaust Fan

Series

The Deluxe Quiet Fire

Rated Exhaust Fan Series

Series combines style

and quiet operation with

a Ceiling Radiation Damper

.

Grill:

Cold rolled steel, powder coated white.

Blower Wheel:

One piece polymeric centrifugal blower wheel,

5

7/32

" diameter

, 2

29

/32

" wide, with 30 blades.

Motor:

Heavy duty

, permanently split capacitor

, 4 pole motor

,

life time lubrication, thermally protected.

Fan Housing:

24 gauge galvanized steel housing.

Duct Collar:

Metal collar for 4" duct connection, comes

complete with built in back draft damper

.

Unit Mounting:

Unit is centered between joists (with 16"

centers) using hanging brackets. The housing will mount

through drywall thickness up to

3/4

".

Damper:

Blanket

- Non-asbestos, ceramic blanket

Fusible Link

- Replaceable, 165

°F standard

Classification

- Ceiling Radiation Damper is ULC classified

and rated for a 3-4 hour fire resistance. U.L. listed 555C.

California State Marshall classification for 1 or 2 hour fire

damper rating. California State Marshall listing number

3225-1374-101.

A

vailability:

Single Packs or sold in Contractor Packs of 4

(Housing, Damper

, Motor/Blade/Grill).

CU

S

Air King V

entilation Products

certifies that the models shown

herein are licensed to bear the

AMCA seal. The ratings shown

are based on tests and procedures

performed in accordance with

AMCA Publication 211 and AMCA

Publication 311 and comply with

the requirements of the Certified

Ratings Program.

CFM/Sones

HVI

Model

Motor

Housing

Damper

@ P

S

.1 WG

RPM

Sones

FRAK80

FAK80T

AKFH2

AKFD2

80/2.6

1250

1.5

FRAK90

FAK90T

AKFH2

AKFD2

90/2.9

1250

2.0

FRAK110

FAK110T

AKFH2

AKFD2

110/3.5

1250

2.5

FRAK130

FAK130T

AKFH2

AKFD2

120/3.6

1250

3.0

Specifications subject to

change without notice.

Advantage 4" Duct

Fire Rated Exhaust

Fan Series

The Advantage 4" Duct

Fire Rated Exhaust Fan

Series combines high

performance with a

Ceiling Radiation Damper

.

Grill:

Cold rolled steel, powder coated white.

Blower Wheel:

One piece polymeric wheel, 5

7/32

" diameter

,

2

3/8

" wide, with 48 blades.

Motor:

Heavy duty

, plug-in, permanently split capacitor

, 4 pole

motor

, life time lubrication, thermally protected.

Fan Housing:

24 gauge galvanized steel housing.

Duct Collar:

Metal collar for 4" duct connection, comes

complete with built in back draft damper

.

Unit Mounting:

Unit is centered between joists (with 16"

centers) using hanging brackets. The housing will mount

through drywall thickness up to

3/4

".

Damper:

Blanket

- Non-asbestos, ceramic blanket

Fusible Link

- Replaceable, 165

°F standard

Classification

- Ceiling Radiation Damper is ULC classified

and rated for a 3-4 hour fire resistance. U.L. listed 555C.

California State Marshall classification for 1 or 2 hour fire

damper rating. California State Marshall listing number

3225-1374-101.

A

vailability:

Single Packs or sold in Contractor Packs of 4

(Housing, Damper

, Motor/Blade/Grill).

CU

S

Air King V

entilation Products

certifies that the models shown

herein are licensed to bear the

AMCA seal. The ratings shown

are based on tests and procedures

performed in accordance with

AMCA Publication 211 and AMCA

Publication 311 and comply with

the requirements of the Certified

Ratings Program.

Performance shown is for FRAK exhaust models for installation type B: Free inlet, Ducted

outlet. Performance ratings include the effects of an inlet grille, ceiling radiation damper

and backdraft damper in the airstream. Speed (RPM) shown is nominal. Performance is

based on actual speed of test. The loudness ratings shown are loudness values in fan

sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA standard 301.

V

alues shown are for installation type B: free inlet fan sone levels. The AMCA Certified

Ratings Seal does not apply to HVI Sones.

CFM/Sones

HVI

Model

Motor

Housing

Damper

@ P

S

.1 WG

RPM

Sones

FRAS90

FA90T

AKFH2

AKFD2

90/3.1

1250

2.5

FRAS120

FA120T

AKFH2

AKFD2

120/3.7

1300

3.0

Specifications subject to

change without notice.

Performance shown is for FRAK exhaust models for installation type B: Free inlet, Ducted

outlet. Performance ratings include the effects of an inlet grille, ceiling radiation damper

and backdraft damper in the airstream. Speed (RPM) shown is nominal. Performance is

based on actual speed of test. The loudness ratings shown are loudness values in fan

sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA standard 301. V

alues

shown are for installation type B: free inlet fan sone levels. The AMCA Certified Ratings

Seal does not apply to HVI Sones.