Remote Power-Off Device — Installation and Quick Start

Configure the Remote Power-Off Device

Types of remote
switches
supported

The RPO supports two types of remote switches:

• A contact closure switch toggles between an open and

closed circuit.

• A voltage input switch applies and removes a voltage

signal.

Set the DIP
switches

On the UPS side of the Remote Power-Off Device, set the DIP
switches labeled CONFIGURATION.

Power-off condition: DIP switches #1 and #2. Use these DIP
switches to configure the power-off condition for the RPO
according to the type of remote switch it is using.

If the positions of DIP switch #1 and DIP switch #2 are both up
or both down, the configuration is invalid.

To connect the remote switch, see “Remote
switch: requirements and pin assignment” on
page 16.

Contact Closure Switch
(Pins 2 and 5)

Setting: DIP
Switch #1

Setting: DIP
Switch #2

A power-off condition occurs
when a normally closed (NC)
contact closure opens.

down

up

A power-off condition occurs
when a normally open (NO)
contact closure opens.

up

down

Voltage Input Switch
(Pins 3 and 4)

Setting: DIP
Switch #1

Setting: DIP
Switch #2

A power-off condition occurs
when 24 V is removed from the
voltage input, resulting in 0 volts.

down

up

A power-off condition occurs
when 24 V is applied to the
voltage input.

up

down