5000/6000 VA models:
Terminal Mode is a menu driven interface that enables enhanced configuration of the UPS.

Connect the serial cable to the serial port on the back of the UPS.

1. Open a terminal program. Example: HyperTerminal

•

From the Desktop, go to Start => Programs => Accessories => Communication
=>HyperTerminal.

2. Double-click on the HyperTerminal icon.

•

Follow the prompts to choose a name and select an icon. Disregard the message, “...must
install a modem,” if it is displayed. Click OK.

•

Select the COM port that is connected to your UPS. The port settings are:

9

bits per second - 2400

9

data - bits 8

9

parity - none

9

stop bit - 1

9

flow control - none

•

Press ENTER

3. Example for setting the number of external battery packs (SURT192XLBP):

Once the blank terminal window is open, follow these steps to enter the number of battery packs:

•

Press ENTER to initiate terminal mode. Press ENTER multiple times, until the prompt User
Name:
is displayed. Follow the prompts. Type slowly, waiting until each character appears
on the screen prior to typing the next character.
Network Management Card

defaults:

•

User Name: apc

•

Password: apc

•

Press 1 and ENTER to select Device Manager.

•

Select the model by entering the corresponding number, then press ENTER.

•

Press 3 and ENTER to select Configuration.

•

Press 1 and ENTER to select Battery.

•

Press 2 and ENTER to change the Battery Settings.

•

Type in the number of external battery packs (four battery modules per pack), then
press ENTER. (Number of packs: 1= internal battery module,
2 = 1 SURT192XLBP, 3 = 2 SURT192XLBP, etc.)

•

Press 3 and ENTER to accept the changes.

•

Press ESC multiple times (5) to return to the main menu.

•

Press 4 and ENTER to log out.