Start-up, Caution – Allied Air Enterprises 4PGE User Manual

Page 10

Advertising
background image

Page 10

506488-01

Issue 1008

START-UP

Pre-Start Check List
Complete the following checks before starting the unit:

1. Check the type of gas being supplied. Be sure it is the

same as listed on the unit nameplate.

2. Make sure that the vent hood has been properly installed.

To Light Burners:
1. Turn off electrical power to unit.

2. Turn the thermostat to lowest setting.

3. Turn the gas control knob, or slide the gas control switch,

to the “ON” position (see Figure 9).

4. Turn on electrical power to the unit.

5. Set the room thermostat to the desired temperature.

(If the thermostat “set” temperature is above room
temperature, the burners will light after the pre-purge
time expires.)

To Shut Down Burners:
1. Turn off electrical power to unit.

2. Turn the gas control knob, or slide the gas control switch,

to the “OFF” position (see Figure 9).

Post-Start Check List
After the entire control circuit has been energized and the
heating section is operating, make the following checks:

1. Check for gas leaks, using soapy solution, in the unit

piping as well as the supply piping.

2. Check for correct manifold gas pressures (see following

Checking and Adjusting Gas Input section).

3. Check the supply gas pressure. It must be within the

limits shown on the rating plate. Supply pressure should
be checked with all gas appliances in the building at full
fire. At no time should the supply pressure during standby
exceed 13" w.c., nor should it be less than 5" w.c. for

For Your Safety Read Before Lighting

natural gas or 11" W.C. for propane gas with the burners
in operation. If gas pressure is outside these limits,
contact the gas supplier for corrective action.

4. Adjust temperature rise to be within the range specified

on the rating plate.

Checking and Adjusting Gas Input
For purpose of input adjustment, the minimum
permissible gas supply pressure is 5" w.c. for natural gas
and 11" w.c. for propane.

Gas input must never exceed the input capacity shown on
the rating plate. The furnace is equipped for natural gas
rated inputs with manifold pressure of 3.5" w.c.

The manifold pressure can be measured by shutting off the
gas, removing the pipe plug in the downstream side of the gas
valve, and connecting a water manometer or gauge. To adjust
the regulator, turn the adjusting screw on the regulator
clockwise to increase pressure and input or counterclockwise
to decrease pressure and input. The final manifold pressure
should not vary more than 0.3" w.c. from the above
specified pressure.
See Figure 9 to assist in locating the
regulator on the gas valve.

Furnace is equipped with a direct ignition control. Do not
attempt to manually light the burners.

CAUTION

Figure 9

Gas Valves

Regulator

Adjustment

Cap

Gas

Control

Knob

Inlet Pressure Tap

1/8" NPT

Outlet Pressure Tap

(Manifold Pressure)

1/8" NPT

Gas Control Switch

Inlet Pressure Tap

1/8" NPT

Outlet Pressure Tap

(Manifold Pressure)

1/8" NPT

Regulator

Adjustment

Cap