Installing the VLS Node into a Rack

NOTE:

If you are installing the node into a telco rack, order the appropriate option kit at the

RackSolutions.com web site:

http://www.racksolutions.com/hp

. Follow the instructions on the web

site to install the rack brackets.

1.

Locate the rail kit, part number 360332–003.

2.

Install the two outer slide rails to the rack. The outer rails are marked “FRONT” and “REAR.”

On both sides of the rack, align the rail holes with the holes in the rack and secure with
thumbscrews.

3.

Attach the inner rails to the sides of the node.

Align the holes in the rail with the round tabs on the side of the node and secure with
thumbscrews.

NOTE:

The inner rails are identical.

The word “FRONT” should face away from the node, but will appear upside-down on one
side.

4.

Align the rails on the node with the rails in the rack and slide the node fully into the rack.

If your rack contains single phase PDUs, you will install the node in rack position 35. If your
rack contains 3–phase PDUs, you will install the node in rack position 33.

5.

Tighten the thumbscrews.

6.

Repeat this procedure to install all of the nodes in the rack. See

“NOTE”

below for details.

NOTE:

If your rack contains single phase PDUs:

Install up to four nodes in the first rack starting in position 35 working up the rack.

Install up to four nodes in the second rack starting in position 35 working up the rack.

If your rack contains 3–phase PDUs:

Install up to six nodes in the first rack starting in position 33 working up the rack.

Install up to two nodes in the second rack starting in position 33 working up the rack.

28