HP Modular Cooling System User Manual

Page 26

Advertising
background image

Installation 26

1.

Route the water hoses from the HP Hook Up Kit through the floor cut-out, and then use a hose wrench to
install each main hose to the MCS 5042 unit. For information on floor cut out dimensions, see the HP

mc-Series 5042 Rack Site Preparation Guide.

2.

Route the two drain hoses to the drain collection system catch basin:

a.

Install and route the blue drain hose into either the condensation return line or the gravity drain
collection system catch basin.

b.

Route the preinstalled clear drain hose into the gravity drain collection system catch basin.

c.

Position the gravity drain collection system below the condensation collection pan, enabling gravity
to draw the water out of the condensation collection pan and into the gravity drain collection system
basin.

3.

Log in to the web interface:

a.

Enter the user name in the User Name field. The default user name is Admin.

b.

Enter the password in the Password field. The default password is Admin.

Advertising
This manual is related to the following products: