Troubleshooting tips – GE ADER50LQ User Manual

Page 8

Advertising
background image

8

Troubleshooting tips…

Save time and money! Review the chart below first and you may not need to call for service.

Problem

Possible Causes

What To Do

Dehumidifier

The dehumidifier

tMake sure the dehumidifier’s plug is pushed completely

does not start

is unplugged.

into the outlet.

The fuse is blown/circuit

t Check the house fuse/circuit breaker box and replace

breaker is tripped.

the fuse or reset the breaker.

Dehumidifier has reached its

t The dehumidifier automatically turns off when either

preset level or bucket is full.

condition occurs. Change to a lower setting or empty

the bucket and replace properly.

Bucket is not in the

t The bucket must be in place and securely seated for the

proper position.

dehumidifier to operate.

Power failure.

t There is a protective time delay (up to 3 minutes) to

prevent tripping of the compressor overload. For this

reason, the unit may not start normal dehumidifying

for 3 minutes after it is turned back on.

Dehumidifier does not

Did not allow enough time

t When first installed, allow at least 24 hours to maintain

dry the air as it should

to remove the moisture.

the desired dryness.

Airflow is restricted.

t Make sure there are no curtains, blinds or furniture

blocking the front or back of the dehumidifier. See the

Choosing a Location section.

Dirty filter.

t See the Care and Cleaning section.

The Humidity Control may

t For drier air, press the ź pad and set to a lower percent

not be set low enough.

value (%) or at CO (continuous) for maximum

dehumidification.

Doors and windows may not

t Check that all doors, windows and other openings

be closed tightly.

are securely closed.

Clothes dryer may be

t Install the dehumidifier away from the dryer.

blowing moisture-laden

The dryer should be vented to the outside.

air into the room.

Room temperature

t Moisture removal is best at higher room temperatures.

is too low.

Lower room temperatures will reduce the moisture

removal rate. Models are designed to be operated at

temperatures above 41°F (5°C).

Dehumidifier runs

Area to be dehumidified

t The capacity of your dehumidifier may not be adequate.

too much

is too large.

Doors and windows are open.

t Close all doors and windows to the outside.

Frost appears on

Dehumidifier has been turned

t This is normal. Frost will usually disappear

the coils

on recently, or room temperature within 60 minutes. See the Automatic Defrost section.

is below 41°F (5°C).

Controls cannot be set

The compressor will turn off

t This is normal. Wait approximately 3 minutes and set the

and the fan will automatically fan as desired.

continue to run for

approximately 3 minutes at a

fixed

setting.

Fan noise

Air is moving through

t This is normal.

the dehumidifier.

Water on floor

Hose connection may be loose. t Check the hose connection. See the Removing Collected

Water section.

Intended to use the bucket to

t Disconnect the hose if using the bucket to collect water.

collect water, but a hose See

the

Removing Collected Water section

as attached.

Bucket Full LED light

Drain hose not tight on fitting

t Check drain hose connection.

flashing and alarm

sounds while drain hose

Drain hose is kinked

t Ensure the drain hose is pointed straight down to the floor

is connected

and is not kinked in anyway.

Consumer Support

Troubleshooting Tips

Operating Instructions

Safety Instructions

Troubleshooting Tips

Care and Cleaning

Safety Instructions

Operating Instructions

Advertising
This manual is related to the following products: