AMX Energy Management Modules RDM-3EM User Manual

Rdm-3em and rdm-6em, Installation sheet, Energy management modules

Advertising
background image

Installation Sheet

RDM-3EM and RDM-6EM

Energy Management Modules

The RDM-3EM (FG606-81) and RDM-6EM (FG606-80) are 3 and 6
channel switching energy management modules. They are designed for use
with the RDA series of enclosures in an AMX Lighting™ system.
For more detailed installation and operating instructions, refer to the Radia
Lighting Control System
Instruction Manual, available on-line at
www.amx.com.
The RDM-3EM and RDM-6EM are designed with the most advanced
latching energy management relays to support heavy duty commercial
applications, building automation, and loadside management. Equipped
with on-board module microprocessors, both support relay control and
sequencing. Features include:

•

User selectable delays in sequencing mode to minimize inrush current

and stress on the electrical distribution system.

•

Selectable strapping facilitates multiple relays on one Radia control

channel for large area control.

•

Manual on/off override on each relay independent of control system.

•

Relays retain their state during power and control system outages.

•

Visual Status Indicators on each relay.

•

Latching relays do not consume any control current, except when they

change state, eliminating the need for additional Radia power supplies.

Specifications

•

Dimensions (HW): 10.00" x 2.75" (25.40 cm x 6.99 cm)

•

Non-phase dependant

•

Use wires rated at 75°C (167°F)

•

Torque terminals to 4.4 in lbs.

•

Wire size: 26 AWG to 10 AWG

•

Wire stripping length: 0.28" (7 mm)

•

Weight: 15 oz. (RDM-3EM) and 1.5 lbs. (RDM-6EM)

Included Accessories

•

4 mounting screws

•

Control wiring harness

RDM-3EM and RDM-6EM UL and C-Ul Ratings

•

General purpose: 120, 240, 277, and 347

*

VAC, 20 A

•

UL/CUL916 Energy Management Systems.

•

UL/CUL508 Industrial Control Systems.

Suggested Switched Loads

•

Incandescent

•

Fluorescent

•

Transformer

•

Low voltage

•

General purpose

Caution: Pre-Installation Notes

•

All Class 1 wiring must be connected to proper terminals.

•

All control wiring must be connected to proper terminals.

•

Disconnect power while installing or connecting the unit.

•

Keep top and bottom air vents clear at all times.

•

Test loads for shorts before connecting.

•

Use low voltage wires with a 300 volt rating or greater.

•

Use field installed copper conductors.

•

All electrical ratings are for continuous duty.

•

For indoor use only.

FIG. 1

RDM-6EM

Mounting
points

Relays

Sequencing
Delay Jumpers
(JP1 and JP2)

Control
Port
Strapping
Jumpers
(JP3 - JP7)

(1-6)

1

2

3

4

5

6

Mounting points

FIG. 2

RDM-3EM

Mounting
points

Relays

Sequencing
Delay Jumpers
(JP1 and JP2)

Control
Port
Strapping
Jumpers
(JP3 - JP4)

(1-3)

1

2

3

Mounting points

*

Agency approval pending