Specifications – Outback Power Systems GFX Series Inverter/Charger Operators Manual User Manual
Page 53

Specifications
900-0114-01-00 Rev A
51
Table 19 48-Volt Inverter Settings
48 Vdc Inverter
Default
Minimum
Maximum
Stacking
Stack Phase
Master
Master,Classic Slave, OB Slave L1, 3p Classic B,
or 3p Classic C
Power Save Level
Master Adjust Only
0 0 7
Slave Adjust Only
1 1 15
Sell
Sell RE Volts
52 Vdc
40 Vdc
60 vdc
Grid Tie Window
User
IEEE or User
Grid Tie Authority
GridTie
GridTie or No Sell
Calibration (Cal)
Vac Input Adjustment1
236 220 254
Vac Output Adjustment1
236 220 254
Battery Vdc Adjustment2
2 0 4
1These values are in digital counts, not volts. Lower counts stand for higher voltages, and higher counts mean lower
voltages. One count equals approximately 1 Vac. The range of adjustment is 15 Vac above nominal, and 17 Vac
below nominal.
2
These values are in digital counts, not volts. One count equals 0.4 Vdc. The range of adjustment is 0.8 Vdc above or
below nominal.