Troubleshooting – Outback Power Systems GS8048 Operator Manual User Manual

Page 40

Advertising
background image

Troubleshooting

38

900-0020-01-00 Rev B

Table 3 Troubleshooting

Symptom

Possible Cause

Possible Remedy

Reduced power sold
to the utility grid.

AC source voltage is driven high
when the inverter sells large

amounts of power.

When the inverter senses a rise in grid voltage while selling, it
reduces the sell current, to avoid forcing the voltage to

unacceptable levels. Check AC input voltage while selling. The

inverter may be behaving correctly.

Loads drop out or

crash during

transfer.

Erratic AC source voltage.

Check AC voltage on the inverter’s input test points. (See page

35.) If not consistent, the problem is external.

MATE3 system display only: AC source voltage may have dipped or
hovered at a low enough point to crash a sensitive load before

the inverter could take over. This can happen if the inverter’s

Grid

AC Input Voltage Limits or Gen AC Input Voltage Limits were
turned down to accommodate a problematic AC source. To make

the inverter respond sooner, raise the lower limit setting in the
appropriate menu. (If this setting was intentional, then no action

is required.)

Inverter set to

Search (Search

mode).

The unit will take a moment to come out of Search mode after

transferring.

MATE3 system display only: If constant power is required, set to

ON with the INVERTER

hot key. (If this setting was intentional,

then no action is required.)

Loads sensitive to inverter’s

transfer time.

UPS mode not in

use on the appropriate input.

MATE3 system display only: Most of the inverter’s input modes

feature a small but noticeable response time during transfer.
Certain loads (such as highly sensitive computers) may not

respond well. The

UPS input mode has a faster response time.

Select this mode for the appropriate input. (See page 12.)

Loads too large.

The unit can transfer more power than it can invert. If loads are

oversized, the unit will falter or crash when switching to batteries.

Reduce the size of the loads.

Undersized battery cables.

Battery cables smaller than recommended will cause a significant

voltage drop when switching to batteries, acting like either an

overload or a low-battery condition. Size all cables correctly.

Unit reads AC input,

even though no

source is present.

Internal transfer relay may be

damaged.

Disconnect AC input wires and turn inverter on. Test the AC input

and neutral test points with an AC voltmeter. (See page 35.) If

voltage appears there, the transfer relay may be jammed. Contact

OutBack Technical Support (see inside front cover of this manual).

This problem is not common. If this occurs, it will likely occur on

only the Grid or Gen input — not both.

Inverter clicks

repeatedly. AC

output voltage rises

or drops to unusual

levels with every

click.

Inverter’s output has been

connected to its input. Voltage

shifts are the result of trying to
match its own voltage.

Disconnect the wires from the inverter’s AC input or AC output

terminals, or both. If the problem immediately disappears, it is an

external wiring issue. The inverter’s AC HOT IN and AC HOT OUT
must remain isolated from each other.

Low AC input voltage. Can be

caused by weak AC source, or

by faulty input connection.

Test AC hot and neutral input test points with an AC voltmeter.

(See page 35.) If low or fluctuating, this is an external problem.

A generator is connected to the

input terminals while the unit is

in the Grid Tied input mode.

The inverter is not intended to sell power to a generator. The

selling activity will drive the generator voltage up to the

disconnection point. It will then reconnect to the generator and
try again. Change input modes, or move the generator to an

input with a different mode selected.

Advertising