Fw-iob-q-230vac parts list, Requirements and warnings – Outback Power Systems FW-IOB-Q-230VAC Input/Output/Bypass Assembly - Installation Instructions User Manual
Page 3

FW-IOB-Q-230VAC Parts List
Figure 1: FW-IOB-Q-230VAC
Hot Conductors (Brown)
Ground Conductor (Green)
Neutral Conductor (Blue)
AC Breakers
Breaker Label Kit
Brown Terminal
AC Breaker Bypass
Blue Terminal
Bus Bar Insulators
Slide Plate
Bus Bar Insulators
Hardware Kit
Bus Bars
Requirements and Warnings
The OutBack FW-IOB-Q-230VAC is intended as a system component and is included in a listing by
ETL as indoor enclosures to UL standard UL 508A Industrial Control Panels.
This enclosure is intended for battery circuits configured for 12 to 48 volts nominal.
Grounding Instructions – Each enclosure should be connected to a grounded, permanent wiring
system. For most installations, the negative battery conductor should be bonded to the grounding
system at one (and only one) point in the DC system. All installations must comply with all national
and local codes and ordinances. System grounding as required by the National Electric Code,
ANSI /NFPA 70-1996, is the responsibility of the system installer.
The equipment ground is marked with this symbol: