Commands – Outback Power Systems MATE3 USB Card Owner’s Manual User Manual

Page 20

Advertising
background image

Commands

18

900-0137-01-00 Rev

A

Table 21

Command/Response Definitions

Command

Response

<SELL:0>

Set inverter Selling disabled

<SELL:1>

Set inverter Selling enabled

<SELL:?>

Returns current inverter sell mode [SELL:s]
s = state,
0=disabled,
1=enabled

<SELLV:nnn>

Sets inverter selling battery voltage where nn.n is the selling voltage

<SELLV:+>

Increments inverter selling battery voltage

<SELLV:->

Decrements inverter selling battery voltage

<SELLV:?>

Returns the selling voltage [SELLV:nnn] when nn.n is the battery selling voltage

<CHG:0>

Set the inverter’s charger(s) off

<CHG:1>

Set the inverter’s charger(s) auto

<CHG:2>

Set the inverter’s charger(s) on

<CHG:?>

Returns current charger mode [CHG:m] for inverter
m = mode,
0=Off,
1=On,
2=Auto

<CHGLM:nn>

Sets inverter’s AC charger limit amps, where nn = AC charger amp limit

<CHGLM:+>

Increments inverter’s charger limits amps

<CHGLM:->

Decrements inverter’s charger limits amps

<CHGLM:?>

Returns inverter’s AC charger limit amps [CHGLM:nn]

<AC1INLM:nn>

Sets inverter’s AC1 input limit amps

<AC1INLM:+>

Increments inverter’s AC1 input limit amps

<AC1INLM:-> Decrements

inverter’s AC1 input limit amps

<AC1INLM:?>

Returns inverter’s AC1 input limit amps [AC1INLM:nn]

<AC2INLM:nn>

Sets inverter’s AC2 input limit amps

<AC2INLM:+>

Increments inverter’s AC2 input limit amps

<AC2INLM:-> Decrements

inverter’s AC2 input limit amps

<AC2INLM:?>

Returns inverter’s AC2 input limit amps [AC2INLM:nn]

<BULK:1>

Starts system wide bulk charge (all ports)

<BULK:2>

Stops system wide bulk charge, ie goto float (all ports)

<BULK:?>

Returns the current bulk charge state [BLK:s] (all ports)
s = state,
s=2 bulk charge stopped,
s=1 bulk charge enabled

<TEMP:p>

Returns inverter’s internal temperatures, p = port 0-10, [TEMP:p,F,C,X]
where p = port 1-10, F=FET, C=CAP, X=Transformer temps in degrees C

If inverter is a Radian series, it returns [TEMP:p, 1st module F=FET, C=CAP, X=Transformer, 2nd
module F=FET, C=CAP, X=Transformer]

Example <TEMP:p> returns [TEMP:1:25,27,20,26,27,28]

<BTEMP:?>

Returns battery temp value in degrees C [BTEMP:nnn] nnn in degrees C, can be a negative value

<ABSORBV:nnn>

Sets system wide absorb voltage nn.n = absorb voltage (all ports)

<ABSORBV:?>

Returns current system wide absorb voltage [ABSORBV:nnn] (all ports)

<ABSORBT:ttt]

Set system wide absorb time in tenths of hours (all ports)

<ABSORBT:?>

Returns system wide absorb time in tenth of hours [ABSORBT:ttt] (all ports)

<FLOATV:nnn>

Sets system wide float voltage nn.n = float voltage (all ports)

<FLOATV:?>

Returns current system wide float voltage [FLOATV:nnn] (all ports)

<FLOATT:ttt] Set

inverter’s float time in tenths of hours (all ports)

<FLOATT:?>

Returns inverter’s float time in tenth of hours [FLOATT:ttt] (all ports)

<FIRM:p>

Returns firmware revision of software for device connected to port p [FIRM:V1.V2.V3]

<FIRM3:?>

Returns MATE3 firmware revision [FIRM3:V1.V2.V3]

Advertising