electrIcal data

General

Check the water heater model and rating plate information against

the characteristics of the branch circuit electrical supply. Do not

connect the heater to an improper source of electricity.

Voltage applied to the heater should not vary more than +5% to -10%

of the model and rating plate marking for satisfactory operation.

Do NOT energize the branch circuit for any reason before the water

heater tank is filled with water. Doing so may cause the heating

elements to fail.

The installation must conform to these instructions and the local

code authority having jurisdiction. Grounding and electrical wiring

connected to the water heater must also conform to the National

Electrical Code, NFPA 70. This publication is available from The

National Fire Protection Association, 1 Batterymarch Park, Quincy,

MA 02269.

branch cIrcuIt

The branch circuit wire size should be established through reference

to the NEC (National Electrical Code) or other locally approved

sources in conjunction with the water heater amperage rating.. Wire

rated at 75°C should be used. For convenience, portions of the wire

size tables from the Code are reproduced in Table 3. It is suggested

the electrician size the branch circuit at 125 percent of the heater

rating and further increase wire size as necessary to compensate

for voltage drop in long runs. Voltage drop should not exceed 3% at

the water heater.

heater cIrcuIts

The water heater’s electrical components are pictured and identified

in the Features and Components illustrations in Figure 2. The model

and rating plate provides heater circuit ratings. There are two main

electrical circuits:

Control Circuit: Power supply for the electromagnetic

contactor coils. 120V power is supplied to the contactor coils

by the CCB (Central Control Board) see wiring diagrams in

this manual.

Power Circuit: High voltage, single or three phase, circuit that

carries the heating element load.

The following section and pages describe the water heater circuits

and includes wiring diagrams.

control cIrcuIts

The water heater is equipped with an electronic control system.

The system includes a CCB (Central Control Board), an immersion

temperature probe with ECO for temperature sensing and limiting, a

UIM (User Interface Module) for user interface & information display

and element current sensors for monitoring the power circuits. Refer

to the control circuit label on the water heater for details. The CCB

is powered by a small 120V/24V transformer. The control circuit

operates on 120V supplied by a larger 100VA transformer.

sequence of operation

1. When the control is powered, the UIM should display model

information, water temperature, operating setpoint, heating

status and operating mode.

2. If the control determines that the actual water temperature inside

the tank is below the programmed operating setpoint minus the

(1st) differential setpoint, a call for heat is activated.

3. After all safety checks are verified the CCB will energize the

contactor coil(s). On models with more than one heating

element the upper most heating elements are energized first.

Successive heating elements are energized according to

programmed differential setpoints for each heating element.

4. The control remains in the heating mode until the water

temperature reaches the programmed operating setpoint. At

this point the contactors will be de-energized.

5. The control system now enters the standby operating mode

while continuing to monitor the water temperature and the state

of other system devices. If the water temperature drops below

the programmed Operating Setpoint minus the (1st) differential

setpoint, the control will automatically return to step 2 and repeat

the heating cycle.

power cIrcuIt

Power circuit wiring is type THHN (or equivalent) rated 600 volts,

105°C, sized as necessary.

The following wiring diagrams are included in this manual to show

typical arrangements of electrical components in the control and

power circuits by voltage and phase characteristics. They are to be

used as a reference by the installer or servicer in performing their

work. An actual diagram of the water heater wiring is furnished with

the heater.