Table 7. technical data venting (continued) – State SBL85 390 NE A User Manual
Page 19
Advertising

19
taBle 7. teChniCal data Venting (Continued)
Model Sbl85390Ne(A)
Input: 390,000 btu/hr
Total Vent Height (Feet)
Vent connector size: 6 inches
6
8
10
15
20
30
50
100
Input (btu/hr)
Rise
Vent Connector Diameter (Inches)
390,000
1 Ft.
-
-
-
-
8
7
7
6
390,000
2 Ft.
-
-
-
8
8
7
7
6
390,000
3 Ft.
-
-
8
8
8
7
7
6
Number of Heaters
Combined Input (btu/hr)
Manifold and Common Vent Diameter (Inches)
2
780,000
12
12
12
10
10
9
9
8
3
1,170,000
16
14
14
14
12
12
10
9
4
1,560,000
16
16
16
14
14
14
12
10