Operating Manual

2003-01-22

1

HUMIDITY TRANSMITTER HMD60U

HUMIDITY AND TEMPERATURE TRANSMITTER HMD60Y

MOUNTING

Ø 12

(0.47)

250 (9.84)

62 (2.44)

100 (3.94)

100 (3.

94)

Mounti

ng

hol

e 82

(3.2

3)>

>

>

Mounting hole 82 (3.23)>>>

The HMD60U/Y humidity and
temperature transmitters are two-wire
transmitters. They are duct mounted, and
the electronics can be disconnected
without dismantling the installation.

Mount the transmitter with two screws.
Place the drilling template on the duct
surface and drill the holes as indicated.
Remember to drill an additional hole for
calibration purposes. The calibration can
be conveniently performed on site with
the HMI41 or HM70 portable indicator
equipped with an appropriate probe and
optional calibration cable.

Figure 1 Dimensions of the HMD60U/Y

GROUNDING

(If the cable diameter is less

than 7mm, use a shrinking
tube or an adhesive tape)

cable

braid

flexible wires 0.5 mm²

(AWG 20), stranded wires

recommended

D = Ø 7...10mm

3

brass
disks

25

rubber

ring

nut

brass disks

140

165

shielding tube

braid

Figure 2 Signal cable grounding with
bushing 18941HM

Open the lid and mount the cable
bushing set 18941HM. Do the grounding
according to Figure 2. W

hen connecting

the signal cable to the transmitter housing,
fold the cable braid between the brass disk
in order to achieve the best EMC per-
formance. Do not leave the bare shield of
the connected wires so that it can
shortcircuit the electronics!