PROGRAMMING MODE ENTRY (PAR KEY)

The meter normally operates in the Display Mode. No parameters can be

programmed in this mode. The Programming Mode is entered by pressing the

PAR

key. If it is not accessible then it is locked by either a security code, or a

hardware lock.

Two types of programming modes are available. Quick Programming Mode

permits only certain parameters to be viewed and/or modified. All meter
functions continue to operate except the front panel keys change to Programming
Mode Operations. Quick Programming Mode is configured in Module 3.

Full Programming Mode permits all parameters to be viewed and modified.

In this mode, incoming counts may not be recognized correctly, the front panel
keys change to Programming Mode Operations and certain user input functions
are disabled. Throughout this document, Programming Mode always refers to
“Full” Programming, unless “Quick Programming” is referenced.

MODULE ENTRY (ARROW & PAR KEYS)

The Programming Menu is organized into nine modules. These modules group

together parameters that are related in function. The display will alternate between



and the present module. The arrow keys (

F1

and

F2

) are used to select

the desired module. The displayed module is entered by pressing the

PAR

key.

MODULE MENU (PAR KEY)

Each module has a separate module menu (which is shown at the start of each

module discussion). The

PAR

key is pressed to advance to a particular parameter

to be changed, without changing the programming of preceding parameters.
After completing a module, the display will return to



. Programming may

continue by accessing additional modules.

SELECTION / VALUE ENTRY (ARROW & PAR KEYS)

For each parameter, the display alternates between the present parameter and

the selections/value for that parameter. The arrow keys (

F1

and

F2

) are used

to move through the selections/values for that parameter. Pressing the

PAR

key,

stores and activates the displayed selection/value. This also advances the meter
to the next parameter.

For numeric values, the

RST

key may be used to select a specific digit to be

changed. Once a digit is selected, the arrow keys are used to increment or
decrement that digit to the desired number.

PROGRAMMING MODE EXIT (DSP KEY or at



PAR KEY)

The Programming Mode is exited by pressing the

DSP

key (from anywhere

in the Programming Mode) or the

PAR

key (with

 

displayed). This will

commit any stored parameter changes to memory and return the meter to the
Display Mode. If a parameter was just changed, the

PAR

key should be pressed

to store the change before pressing the

DSP

key. (If power loss occurs before

returning to the Display Mode, verify recent parameter changes.)

PROGRAMMING TIPS

It is recommended to start with Module 1 and proceed through each module

in sequence. If lost or confused while programming, press the

DSP

key and start

over. When programming is complete, it is recommended to record the
parameter programming on the Parameter Value Chart and lock out parameter
programming with a user input or lock-out code.

FACTORY SETTINGS

Factory Settings may be completely restored in Module 9. This is a good

starting point if encountering programming problems. All factory settings are
listed on the Parameter Value Chart following the Programming section.

ALTERNATING SELECTION DISPLAY

In the explanation of the modules, the following dual display with arrows will

appear. This is used to illustrate the display alternating between the parameter
on top and the parameter’s Factory Setting on the bottom. In most cases,
selections or value ranges for the parameter will be listed on the right.

6.0 P

ROGRAMMING

THE

M

ETER

Parameters

and B Setup

Totalizer A

4-tot

Parameters

Setup

1-rAtE

Pro

DISPLAY

MODE

Lock-out

Key

2-FNC

Parameters

3-LOC

Parameters

Function

Program

Communications

(Alarm)

Setup

6-SPt

5-totC

7-SrL

Parameters

Setpoint*

Serial*

Service

Output

9-FCS

8-AnA

Parameters

Factory

Analog*

Parameters

Parameters

Operations

Rate

User Input/

NO

* Only accessible with appropriate plug-in card.

PAR

F1/F2

Keys

Display/

PAR

PAR

PAR

PAR

PAR

PAR

PAR

PAR

PAR

Totalizer C

OVERVIEW

PROGRAMMING MENU

Indicates Program Mode Alternating Display

Factory Settings are shown.





Parameter

Selection/Value