Example 1:

A PAXLCL is to be calibrated to match a flow transducer whose output is 10

mA @ 0 GPM and 50 mA @ 1375 GPM.

READOUT SPAN (Rs) = 1375

 0 = 1375

SWING CURRENT (Is) = 50 mA

 10 mA = 40 mA

ADJUSTMENTS (Refer to the transfer curve below)

Null the unit to zero readout @ 0

current per Steps 1 to 4 of the
calibration steps.

Set the coarse and fine span adjustments

to get a readout of 1375 @ 40 mA per
Steps 5 and 6. Note: With the full
standard swing of 40 mA, the coarse
span switch reference markings can be
used to determine settings as follows:

S7 ON (1050) + S9 ON (260) = 1310

Span set with switches.

375 (needed) - 1310 (with SW’s) = 65

w. fine span adj.

Set offset to readout 0 @ 10 mA per Step 7. Note: The read out observed

when the 10 mA min. current is first applied can be used to determine the
offset switch settings.)
In this example the readout will be (+) 344 when the
10 mA min. current is first applied. Applying -344 offset then reduces the
readout to zero @ 10 mA.

Check readout at max. (50 mA) and min. (10 mA) and fine tune (tweak) as

required per Step 8.

Example 2 (Negative Slope):

A level measuring device puts out 6 mA when a storage tank is full and 15

mA when the tank is empty. The PAXLCL is to readout 90.0 tons at full tank
and zero when empty.

READOUT SPAN (Rs) = 900

 0 = 900 (Disregard Decimal Points)

SWING CURRENT (Is) = 6 mA (@ max rdg) - 15 mA (@ min rdg) = -9 mA

In this case, the signal current is reverse [Term 3 (-) with respect to Term 5
(+)] causing the readout to go “down” (increasingly negative) as the negative
current increases.

ADJUSTMENTS

Null the unit per Steps 1 to 4.

Set slope of transfer curve with span

adjustments to get readout of -900
@ -9 mA per Steps 5 and 6.

Move transfer curve up by applying

(+) offset per Step 7 until readout is
+900 @ -6 mA.

Check extreme readings per Step 8,

0 readout @ -15 mA and +900
readout @ -6 mA. Set D.P. Switch
S1 and replace unit in case.

Example 3 (± Display):

A differential pressure transducer has a range of ±1500 PSI with a 4 to 20 mA

output (-1500 @ 4 mA, +1500 @ 20 mA).

READOUT SPAN (Rs) = +1500

(1500) = 3000

SWING CURRENT (Is) = 20 mA(max) - 4 mA(min) = 16 mA

Note: Since the display readout is limited to 1999 numerical indication, the

full READOUT SPAN of 3000 cannot be obtained during zero based span
adjustment. However, dividing both the READOUT SPAN and SWING
CURRENT by two, i.e. 1500 readout @ 8 mA, allows the span adjustment
to be made for the proper transfer curve slope.

ADJUSTMENTS

Null the unit per Steps 1 to 4.

Set transfer curve slope with span

adjustments per Steps 5 and 6, to get
a readout of +1500 @ 8 mA.

Apply (-) offset per Step 7 to get a

reading of -1500 @ 4 mA.

Check min. and max. extremes and

tweak if required to get desired
readout @ 4 and 20 mA per Step 8.

1375

OFFSET

READOUT

NULL

40

B SPAN

10

50

MA

MA

MA

CURRENT

D

CHECK

C

A

6.0 A

PPLICATIONS

C

A

D

CHECK

READOUT

B

CURRENT

(+)

(-)

-15

MA

-9
MA

-6
MA

-900

+900

OFFSET

NULL

SPAN

SPAN

OFFSET

CURRENT

(-)

4

MA

B

8

MA

20

MA

-1500

NULL

A

(+)

C

READOUT

+1500

D

CHECK

CHECK

D

Red Lion Controls
Headquarters
20 Willow Springs Circle
York PA 17406
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839

Red Lion Controls

China

Unit 101, XinAn Plaza

Building 13, No.99 Tianzhou Road

ShangHai, P.R. China 200223

Tel +86 21 6113-3688

Fax +86 21 6113-3683

Red Lion Controls

Europe

Printerweg 10

NL - 3821 AD Amersfoort

Tel +31 (0) 334 723 225

Fax +31 (0) 334 893 793

Red Lion Controls

India

54, Vishvas Tenement

GST Road, New Ranip,

Ahmedabad-382480 Gujarat, India

Tel +91 987 954 0503

Fax +91 79 275 31 350

Advertising