All-in-one

8.0 Troubleshooting

In the event of malfunction or faulty operating performance check that the installation and
adjustment work has been carried out and completed in accordance with these Operating
Instructions.

If malfunctions cannot be eliminate with the help of the following table
9.0 troubleshooting table”, the supplier or manufacturer should be consulted.

9.0 Troubleshooting table

-

ATTENTION !
It is essential that the safety regulations are observed when identifying faults.

ATTENTION !
- refer to item 10.0 and 11.0 prio
r to dismantling and repair work!
- refer to item 6.0 befo
re restarting the plant !

Fault

Possible cause

Corrective measures

No flow

Installed in wrong flow direction

Fit valve in direction of flow arrow

Flange covers not removed

Remove flange covers

at series 63A:
Ball float (pos. 24.16) defective

Check lifting force

Little flow

Piping system clogged

Check piping system

Strainer clogged (pos. 2)

Clean / replace strainer;
refer to item 7.4

Wrong controller size choosen

Correct selection acc. to flow diagram

Changed upstream pressure or back
pressure operating conditions

Correct selection acc. to flow diagram

Wrong installation position

Note installation position;
refer to item 5.3!
Correct installation position;
refer to item 7.5

No closure, or internal
leakage

Shut-off valve clogged

Clean shut-off valve; refer to item 7.1

Shut-off valve worn

Replace shut-off valve; refer to item 7.1

Shot-off valve operated above safe oper-
ating pressure

Observe operating limits as per data
sheet

Controller clogged

Clean strainer and controller;
refer to item 7.4

Controller worn out

Replace controller; refer to item 7.4

Controller incorrectly screwed into body Check seal face between body and con-

troller, tighten controller correctly ; refer
to item 7.6

Diaphragm capsule (pos. 4) clogged

Clean strainer and diaphragm capsule;
refer to item 7.4

Diaphragm capsule worn out

Replace diaphragm capsule;
refer to item 7.4

Seat (pos. 3) incorrectly screwed into
body

Check seal face between body and seat,
tighten seat correctly; refer to item 7.6