9.0 Troubleshooting

In the event of malfunction or faulty operating performance check that the installation and
adjustment work has been carried out and completed in accordance with these Operating
Instructions.

If malfunctions cannot be eliminate with the help of the following table „10.0
Troubleshooting table
“, the supplier or manufacturer should be consulted.

10.0 Troubleshooting table

ATTENTION !
It is essential that the safety regulations are observed when identifying faults.

ATTENTION !
- read point 7.0 and 8.0 prior to
dismantling and repair work !
- read point 6.0 before restarting the plant !

Fault

Possible causes

Corrective measures

Actuator unit does not move

No compressed air on the control
pressure line

Discern the causes and remedy

Actuator unit has been improperly
installed

Check the actuator’s operating
mode and connect to the control
pressure line in accordance to this
operating mode.

The rolling diaphragm is defect

Let replace the rolling diaphragm
and springs

Manual emergency adjustment is
blocked

Set the manual emergency
adjustment into the correct position
(both position indicators must be at
the starting point and be in the same
position).

There is not enough positioning
force available

Wrong spring pieces
(the spring range of the actuator is
wrong)

Let replace springs (actuator unit)

Stem sealing has a leak

Let renew the stem sealing

The ventilation is plugged and the air
cannot escape from the actuator unit

Screw cap must be disengaged

The actuator unit does not ventilate
sufficiently

Check the control adjutment