Installation and Maintenance Manual

Chapter 3: Programming

Chapter 3: Programming

3.1: Security Input

The security input is often referred to as the “Run/Program” input. This input is located on the 16-place

terminal strip and is discussed in Chapter 4: Expansion Modules. This input prevents unauthorized

changes to the programmed functions. With the unit in the “Program” mode, all functions of the control-

ler can be programmed. With the unit in the “Run” mode, all setpoints, motion detect and other opera-

tional functions can be verified, but the programmed information cannot be changed.

3.2: Initialization

The following key commands should be entered on the

keypad to clear all programmed data upon installation and PRIOR to programming. This sequence

clears all programmed data. All operating parameters must be reprogrammed after using this initializa-

tion function.

3.3: Scale Factor

ENT

CIR# - 9 - 9

5

-

-

The 1995B is available only with a 360 degree scale factor, set permanently.

3.4: Number of Outputs

The 1995B comes programmed for five outputs, but it is expandable to 29 outputs. However, when

using a Remote Circular Display, the maximum will be 23 outputs.