Electronic Controller Solutions for the Global Fluid Power Industry

epc-2 & evc-2 User Interface ‘Fine Settings Page’ Guide:

1. Channel X coil 1A Imin Out Current ( mA ):

Minimum value allowed = 0mA

This is the minimum current value that that will be sent to valve

coil 1A when the command signal is approximately ± 5% of 2.5V

(~125mV)

2. Channel X coil 1A Imax Out Current (mA):

Maximum value allowed = 3000mA

This is the maximum current value that that will be sent to valve

coil 1A when the command signal is at approximately ±100%

i.e. 0% command = Coil B at 100%, 50% command - Both coils

OFF, 100% command = Coil A at 100%.

3. Channel X coil 1B Imin Out Current (mA):

Same function and action as noted in item 1. above

4. Channel X coil 1B Imax Out Current (mA):

Same function and action as noted in item 2. above

5. Channel X coil 1A Ramp UP time ( Seconds ):

Minimum value allowed = 0 seconds - Maximum value allowed = 65 seconds

This is the total time taken for the output current to go between the Imin and Imax settings for a 0% to 100% command input.

The time is scaled for 0 to 100% command meaning that if the command goes from 50% to 100% the time taken will be

50% of the seconds set.

6. Channel X coil 1A Ramp DOWN time ( Seconds ):

Minimum value allowed = 0 seconds - Maximum value allowed = 65 seconds

This is the total time taken for the output current to go between the Imax and Imin settings for a 100% to 0% command input.

The time is scaled for 0 to 100% command meaning that if the command goes from 100% to 50% the time taken will be

50% of the seconds set.

7. Channel X coil 1B Ramp UP time ( Seconds ):

Minimum value allowed = 0 seconds - Maximum value allowed = 65 seconds

Same function and action as noted in item 5. above

8. Channel X coil 1B Ramp DOWN time ( Seconds ):

Minimum value allowed = 0 seconds - Maximum value allowed = 65 seconds

Same function and action as noted in item 6. above

9. Channel X Dither Amplitude:

Minimum value allowed = 0% - Maximum value allowed = 100% ( in 10% increments )

This is the level of ‘Dither’ signal applied to the output current as a fixed percentage - i.e. if you set 50% here, the amplitude

will be ratiometric over the entire PWM output range of 5 to 95 PWM.

Valve OEM’s usually recommend a % level here If no information is available, set to 30% for initial trials and optimize at

later stage if needed.

10.

Channel X Dither Frequency ( Hz ):

pre-set values - 33, 45, 50, 55, 76, 100, 125, 142, 200, 250, 333 & 500HZ

This is the ‘Dither’ frequency that will be on the PWM output.

Valve OEM’s usually recommend a frequency here, if no information is available, initially set 140Hz - 250Hz for

cartridge and smaller valves and 100Hz - 140Hz for larger industrial valves.

11. Channel X Command Min:

The value entered here, sets the Minimum command input allowed. Below this value, the respective evc-2 proportional

output is disabled

12. Channel X Command Mid:

The value entered here, sets the Mid command for crossover in dual coil mode, ignored for single coil mode

13. Channel X Command Max:

The value entered here, sets the Maximum command input allowed. Above this value, the respective evc-2 proportional

output is disabled