Double/single/single solenoid control (drf4-vxx), Drf4, Closed-loop valve controller – High Country Tek DRF Series User Manual

Page 21

Advertising
background image

021-DRF Rev A

DRF User Manual

21

Copyright © High Country Tek, Inc.

– 2013

DRF

Closed-loop Valve Controller

Double/Single/Single Solenoid Control (DRF4-Vxx)

The DRF drives a dual-coil valve with joystick input J5-1 and 2
single-coil valves with joystick input J6-1 and J6-3.

Set the dither and output settings according to the valve
specifications.

Schematic

FUSE

+V Power Input
9 - 32VDC

+V = Enabled

PWR J1-1

DRF4

Electronic Valve

Controller

Enable J1-3

GND J1-2

-10V Ref. Out J4-1

+10VDC @ 20mA

0-10VDC

+10V Ref. Out J4-3

Ch. 1 I/P J5-1

V

D

C

I/

P

m

A

I/

P

Supply Voltage

4-12mA

Ch. 2 I/P J5-3

+10VDC @ 20mA

0-10VDC

Ch. 3 I/P J6-1

Sig GND J6-2

V

D

C

I/

P

m

A

I/

P

Supply Voltage

4-20mA

Ch. 4 I/P J6-3

Prop. PWM (Sourcing)

Ch. 3 Out J3-1

Sig GND J3-2

Ch. 4 Out J3-3

Prop. PWM (Sourcing)

+10VDC @ 20mA

0-10VDC

V

D

C

I/

P

m

A

I/

P

4-20mA

Supply Voltage

Sig GND J4-2

J5-2

Prop. PWM (Sourcing)

Ch. 2 Out J2-3

Prop. PWM (Sourcing)

Ch. 1 Out J2-1

Sig GND J2-2

0 to -10VDC

12-20mA

Example Settings

Parameter

Value

C1 Mode

2 CUR USE ENBL

C1 Min input

0.2 V

C1 Max input

10.0 V

C1 Min output

5 mA

C1 Max output

600 mA

C1 Ramp up

1 S

C1 Ramp down

1 S

C2 Mode

4 IN1 USE ENBL

C2 Min input

-0.2 V

C2 Max input

-10.0 V

C2 Min output

5 mA

C2 Max output

600 mA

C2 Ramp up

0 S (NOT USED)

C2 Ramp down

0 S (NOT USED)

C3 Mode

2 CUR USE ENBL

C3 Min input

0.2 V

C3 Max input

10.0 V

C3 Min output

5 mA

C3 Max output

600 mA

C3 Ramp up

1 S

C3 Ramp down

1 S

C4 Mode

2 IN4 USE ENBL

C4 Min input

0.2 V

C4 Max input

10.0 V

C4 Min output

5 mA

C4 Max output

600 mA

C4 Ramp up

1 S

C4 Ramp down

1 S

Dither frequency

150 Hz.