Electric, Electrical service specifications, A. gas models only – American Dryer Corp. AD-24 Phase 7 User Manual

Page 21

Advertising
background image

113222 - 5

www.amdry.com

17

2. Electrical Service Specifications

IMPORTANT: Figures shown are for non-reversing models only. For reversing models contact

the factory.

a. Gas Models Only

* 3-Wire is available.

6/3/08

* 3-Wire is available.

6/3/08

b. Electric Models Only

ALL electrically heated dryers must be connected to the electric service shown on the dryer’s data label.
The connecting wires must be properly sized to handle the rated current.

Gas

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT:

NOTES: A.

B.


C.

208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering,
specify
exact voltage.

When fuses are used they must be dual element, time delay, current

limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse

value, by applying either local and/or National Electrical Codes to

listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type
ONLY. For others, calculate/verify correct breaker size according to
appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

CIRCUIT

BREAKER

60 Hz

50 Hz

120

1ш

2

8.7

—

15

208

1ш

2

5.2

—

15

240

1ш

2

4.8

5.8

15

208

3ш

3

3.0

—

15

240

3ш

3

3.2

3.6

15

380-400

3ш

4*

—

2.2

15

416

3ш

4*

—

2.3

15

460/480

3ш

3

2.1

—

15

Electric

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT:

NOTES: A.

B.


C.

208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering,
specify
exact voltage.

When fuses are used they must be dual element, time delay, current

limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse

value, by applying either local and/or National Electrical Codes to

listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY. For others,
calculate/verify correct breaker size according to appliance amp draw
rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

CIRCUIT

BREAKER

60 Hz

50 Hz

18 kW

208

1ш

2

92

—

125

240

1ш

2

—

81

110

240

1ш

2

80

—

100

208

3ш

3

55

—

70

240

3ш

3

48

—

60

20 kW

208

1ш

2

101

—

150

240

1ш

2

88

—

110

24 kW

208

3ш

3

72

—

90

240

3ш

3

63

—

80

416

3ш

4*

—

39

50

460

3ш

3

32

—

40

480

3ш

3

31

—

40