Table 12: LIST OF RULES

#

Rule

Description

Parameters

00 Relay Off

Turns Relay OFF.

None

01 On_Bat

Activates when UPS is on
Battery Mode.

None (Use Rule#16 if you are using UPS in the
Offline(Standby) Mode to Cabinet Flash.)

02 Low_Bat_1

Activates when batteries reach
user settable capacity level.

Set battery capacity
in %

03 Bat_Timer_1

Activates after user settable
time when UPS is in Battery
mode.

Set Timer in HH:MM:SS

04 Alarms_1

Activates

when

Alarm

conditions occur.

See Alarm/Fault Table
Allows you to choose which alarms you want to
activate this condition. You may choose all or just
some.

05 Faults_1

Activates

when

Fault

conditions occur.

See Alarm/Fault Table

06 Low_Bat_2

Additional Low_Bat condition.
Functions same as Low_Bat_1.

Set battery capacity in %

07 Bat_Timer_2 Additional

Bat_Timer

condition. Functions same as
Bat_Timer_1.

Set Timer in HH:MM:SS

08 Alarms_2

Additional Alarm condition.
Functions same as Alarms_1.

See Alarm/Fault Table

09 Faults_2

Additional Fault condition.
Functions same as Faults_1.

See Alarm/Fault Table

10 Low_Bat_3

Additional Low_Bat condition.
Functions same as Low_Bat_1.

Set battery capacity in %

11 Bat_Timer_3 Additional

Bat_Timer

condition. Functions same as
Bat_Timer_1.

Set Timer in HH:MM:SS

12 Alarms_3

Additional Alarm condition.
Functions same as Alarms_1.

See Alarm/Fault Table

13 Faults_3

Additional Fault condition.
Functions same as Faults_1.

See Alarm/Fault Table

14 Fan_Ctrl_1

Activates

at

Temperature

levels set by user.

Set Hi/Lo limits. Choose from internal sensor or
external(Aux) sensor. There is a minimum Five°C
differential limit between the HI and Low limts.

15 Fan_Ctrl_2

Additional Fan Control
condition.

Set Hi/Lo limits. Choose from internal sensor or
external(Aux) sensor.

16 UTILFAIL_IM Activates

immediately

when

UPS goes to battery mode.

None (Used to activate Flash when in the
Offline(Standby) Mode)