Horner APG XLt OCS HEXT240C015 User Manual

Page 4

Advertising
background image

MAN0873-06-EN

Specifications / Installation

__________________________________________________________________________________________________________________________________________________________________
12/18/2008

Page 4 of 4 ECN # 947

7

Digital Filtering for Analog Inputs

9

Safety


The digital filter is updated once per conversion. It is an “IIR” running average filter
that emulates a simple RC filter. The equivalent time constant is determined by the
Filter Constant and the sum of the conversion times for the two channels. The Filter

When found on the product, the following symbols specify:

two input mode selections. This filter delay is in addition to the PLC scan delay.


Constant determines the weight given to the most recent conversion.

The following table lists the equivalent time constant for the three possible total

Warning: Consult
user documentation.

Warning: Electrical
Shock Hazard.

conversion times, which are dependent upon the

This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or
Non-hazardous locations only

Equivalent RC Time Constant in Seconds

(Nominal time to reach 63% of final value.)

Total Conversion Time in Seconds

WARNING – EXPLOSION HAZARD – Substitution of components may impair
suitability for Class I, Division 2

Filter Constant 0.03 0.09

0.13

0* 0.03*

0.09*

0.13*

AVERTISSEMENT - RISQUE D'EXPLOSION - LA SUBSTITUTION DE
COMPOSANTS PEUT RENDRE CE MATERIAL INACCEPTABLE POUR LES
EMPLACEMENTS DE CLASSE 1, DIVISION 2

1 0.07

0.18

0.27

2 0.13

0.35

0.53

3 0.27

0.71

1.07

4 0.53

1.41

2.13

WARNING – EXPLOSION HAZARD – Do not disconnect equipment unless power
has been switched off or the area is known to be non-hazardous.

5 1.07

2.83

4.27

6 2.14

5.65

8.54

AVERTISSEMENT - RISQUE D'EXPLOSION - AVANT DE DECONNECTOR
L'EQUIPMENT, COUPER LE COURANT OU S'ASSURER QUE
L'EMPLACEMENT EST DESIGNE NON DANGEREUX.

7 4.28

11.30

17.08

* No filter delay, reading is unfiltered conversion value

WARNING: To avoid the risk of electric shock or burns, always connect the safety
(or earth) ground before making any other connections.

8

Thermocouple Grounding Schemes

WARNING: To reduce the risk of fire, electrical shock, or physical injury it is
strongly recommended to fuse the voltage measurement inputs. Be sure to locate
fuses as close to the source as possible.


WARNING: Replace fuse with the same type and rating to provide protection
against risk of fire and shock hazards.


WARNING: In the event of repeated failure, do not




























10 Technical

Support

For assistance and manual updates, contact Technical Support at the following
locations:

North America:
(317) 916-4274
www.heapg.com
email:

[email protected]

Europe:
(+) 353-21-4321-266
www.horner-apg.com
email:

[email protected]

replace the fuse again as a

repeated failure indicates a defective condition that will not

clear by replacing the

fuse.

WARNING: Only qualified electrical personnel familiar with the construction and
operation of this equipment and the hazards involved should install, adjust,
operate, or service this equipment. Read and understand this manual and other
applicable manuals in their entirety before proceeding. Failure to observe this
precaution could result in severe bodily injury or loss of life.



Ungrounded Thermocouples

Ungrounded Thermocouples

Alternate Shield Connection for

Ungrounded Thermocouples.

Preferred Shield Connection for

Ungrounded Thermocouples.






















No part of this publication may be reproduced without the prior agreement and
written permission of Horner APG, Inc. Information in this document is subject to
change without notice.

Š All applicable codes and standards need to be followed in the installation of this
product.
Š Adhere to the following safety precautions whenever any type of connection is
made to the module:
ƒ Connect the safety (earth) ground on the power connector first before making any
other connections.
ƒ When connecting to electric circuits or pulse-initiating equipment, open their
related breakers.
ƒ Do not make connections to live power lines.
ƒ Make connections to the module first; then connect to the circuit to be monitored.
ƒ Route power wires in a safe manner in accordance with good practice and local
codes.
ƒ Wear proper personal protective equipment including safety glasses and insulated
gloves when making connections to power circuits.
ƒ Ensure hands, shoes, and floor are dry before making any connection to a power
line.
ƒ Make sure the unit is turned OFF before making connection to terminals.
ƒ Make sure all circuits are de-energized before making connections.
ƒ Before each use, inspect all cables for breaks or cracks in the insulation. Replace
immediately if defective.
• Use Copper Conductors in Field Wiring Only, 60/75° C

This device complies with part 15 of the FCC Rules. Operation is subject to the
following two conditions:

1. This device may not cause harmful interference.
2. This device must accept any interference received, including interference

that may cause undesired operation.

Grounded Thermocouples

Grounded Thermocouples

Field Ground Potential Less Than Seven Volts AC

Field Ground Potential Less

Than Seven Volts AC

Shields Connected at One End Only May be Used to

Reduce Noise

Typical Shield Connection for

Grounded Thermocouples

Grounded Thermocouples May Use the Ungrounded

Thermocouple Shield Connections if the Shield is not

Grounded at the Field End

Note: The examples for thermocouple grounding schemes above are generic illustrations.

The XT105 has two thermocouple inputs.

Advertising
This manual is related to the following products: