CH. 14
MAN0890-02-EN
August 20, 2009
Page 74 of 96
ECN # 979
14.2 Settings
To use the fail – safe feature, the user needs to do the following:
1. Backup the current Battery-Backed RAM Register contents in On-Board Flash memory using
System Menu options.
2. From Cscape, create AUTOLOAD.PGM for the application program using ‘Export to Removable
Media’.
3. Place the Removable Media with AUTOLOAD.PGM in the device.
4. Set the ‘Enable AutoLoad’ option in the device to YES.
5. Set the ‘Enable AutoRun’ option to YES if the controller needs to be placed in RUN mode
automatically after automatic restore of data or AutoLoad operation.
14.3
Backup / Restore Data
Figure 14.2 – Backup/Restore Data System Menu