PAGE 60

15 MAR 2003

CH.6

MAN0305-02


6.9

SmartStix I/O Module Produced (Transmitted) Global Data

Table 6.12 – Produced Global Data Word 1

16-bit Word

8-bit High Byte

8-bit Low Byte

Digital Input Status Data - Low Word

I16

I15

I14

I13

I12

I11

I10

I9

I8

I7

I6

I5

I4

I3

I2

I1


I16…I1

Monitors the Off / On state of the SmartStix I/O Module’s 1st 16 Digital Inputs, if any.

Table 6.13 – Produced Global Data Word 2

16-bit Word

8-bit High Byte

8-bit Low Byte

Digital Input Status Data - High Word

I32

I31

I30

I29

I28

I27

I26

I25

I24

I23

I22

I21

I20

I19

I18

I17


I32…I17

Monitors the Off / On state of the SmartStix I/O Module’s 2nd 16 Digital Inputs, if any.

Table 6.14 – Produced Global Data Word 3

16-bit Word

8-bit High Byte

8-bit Low Byte

Module Fault Data

Network Fault Data

Configuration Status Data

PUP

I/O

ROM

RAM

LIFE

ID

DUP

NAK

SIT

SHT

SLT


SLT

CLT command status; matches CLT when command is complete

SHT

CHT command status; matches CHT when command is complete

SIT

CIT command status; matches CIT when command is complete


NAK

Network Acknowledge test failed; found no other Network devices

DUP

Network Duplicate ID test failed; found another Network device with our Network ID

ID

Network ID test failed; Network ID rotary switches illegally set to 00, FE or FF

LIFE

Network Life Expectancy Time has expired; outputs are in default state


RAM

Module RAM test failed; found a RAM memory fault during power-up-self-test

ROM

Module ROM test failed; found a ROM memory fault during power-up-self-test

I/O

Module I/O test failed; found an I/O fault during power-up-self-test

PUP

Module just powered up; using default configuration; outputs are Off

Table 6.15 – Produced Global Data Word 4

16-bit Word

8-bit High Byte

8-bit Low Byte

Firmware Revision Status Data

Device Identification Status Data

0.00 to 2.55 = Version Number

0 to 255 = Device Class Number


Device Class Number

SmartStix I/O Module’s numeric product identifier (see

Table 6. 3

).

Version Number

SmartStix I/O Module’s numeric firmware identifier


6.10

Produced Global Data Power-Up Initialization


At power-up, a SmartStix I/O Module’s four Produced Global Data words are initialized as follows:

1. Digital Inputs are read and loaded into Words 1 and 2.
2. Power-up-self-test result is loaded into Word 3; if tests passed, only PUP bit is On.
3. Module’s Device Class Number and Version Number are loaded into Word 4.
4. All four Produced Global Data words are transmitted to the CsCAN Network.