Campbell Scientific AVW1 and AVW4 Interfaces for Vibrating Wire Sensors User Manual

Page 19

Advertising
background image

AVW1/AVW4

4-3

03:

P28

Vibrating Wire (SE)

01:

1

Rep

02:

2

IN Chan

03:

1

Excite all reps w/EXchan 1

04:

24

Starting Freq. (units=100 Hz)

05:

31

End Freq. (units=100 Hz)

06:

500

No. of Cycles

07: 0000

Rep delay (units=.01sec)

08:

2

Loc [:PRESS psi]

09:

-15.1

Mult

10:

142.4

Offset

04:

P34

Z=X+F

01:

1

X Loc TEMP C

02:

-24

F calibration "Temp." in C

03:

4

Z Loc [:(T-To)*C]

05:

P37

Z=X*F

01:

4

X Loc (T-To)*C

02:

-.0698

F "Temp. Coeff."

03:

4

Z Loc [:(T-To)*C]

06:

P33

Z=X+Y

01:

2

X Loc PRESS psi

02:

4

Y Loc (T-To)*C]

03:

3

Z Loc [:Pt psi]

07:

P37

Z=X*F Converts psi to
negative ft H20

01:

3

X Loc Pt psi

02:

-2.3067

F

03:

5

Z Loc [:-Pt FEET H20]

08:

P34

Z=X+F Adds the Offset to the
negative of the Reading to
obtain the Distance from lip of
the well to water surface.

01:

5

X Loc -Pt FEET H20

02:

102.06

F OFFSET

03:

6

Z Loc [:DISTANCE FEET]

09:

P

End Table 1

First 99 Input Location Labels:
1:TEMP C
2:PRESS psi
3:Pt psi
4:(T-To)*C
5:Pt Ft H20
6:DISTAN FT