Campbell Scientific LR4 Four Channel Latching Relay Module User Manual

Page 12

Advertising
background image

LR4 Four Channel Latching Relay Module


SDI-12 Command

Command
Function/Description


Values Returned

aMC!
aMCn!

Same as aM!

aC! Concurrent

Measurements

Status All 4 Relays - 0 or 1
State

R1, R2, R3, R4 (4
values)

aCn!

Concurrent

Measurements

Same as M1 – M8

Output is the
Same as M1 – M8

aCC!
aCCn!

Concurrent Measurement
Commands with Checksum.
See aM and aM1- aM8

Output is the same
as
aM, aM1-aM8
Checksum is added

aD0!

Send Data

Dependent upon
command Sent

aV! Verification

command

S1,S2,V,WD

S1 = BootRom
Signature
S2 = Firmware
Signature
V = Supply
Voltage

Note1

WD = Watch Dog
Errors

aI! Send

Identification

013CAMPBELL
LR4 2.0SN
SN = Serial number
(5 digits)

?! Address

Query

a

aAb!

Change Address command

b is the new address

aXR;0,R1,R2,R3,R4!
Extended
command

Sets Values of All 4 Relays to
either 0 or 1 state
Where R1 is 0 or 1 for Relay #1
Where R2 is 0 or 1 for Relay #2
Where R3 is 0 or 1 for Relay #3
Where R4 is 0 or 1 for Relay #4

a
Address is returned
with a value of 1.

aXR;N,V!
Extended
command

Set the State of an Individual
Relay.
N is 1-4 corresponding to
Relays #1 to #4,
V is 0 or 1 state

a
Address is returned
with a value of 1.

aR0!

Same as aM!

Same as aM!
command

aR1! to aR8!

Same as aM1! to aM8!

Same as M
commands


Where a = address of SDI-12 device.
Where n = numbers 1 to 9

6