AMX ViewStat User Manual

Page 31

Advertising
background image

ViewStat Installation and Wiring

25

ViewStat Communicating Thermostat

6.

After the address has been selected, press the Enter button to store the address.

7.

Use the Scroll Up and Scroll Down buttons to set the "Number of Stats on the Network" to the highest
address that will be on the thermostat network. This will be equal to the total number of thermostats on
the network (unless one or more addresses are skipped - see step 5).

8.

Press Enter to set the baud rate. The ViewStat must be set for 9600 baud to communicate with the
miniverter. This is the default setting, and you shouldn’t ever change this setting.

9.

Press Enter to "Exit" the Communications Set Up sub-menu. This will return you to the main menu.

10.

Press the Scroll Down button until "Exit" is displayed. Press the Enter button. The thermostat will then
reset and return to normal operation.

FIG. 17

Setting the thermostat address

Network Address

Communications

Set Up

More

Set Thermostat

Address

EXIT

Back

1 to 64

Next

No.of T-stats On
the Network

Set Baud

Rate

More

Select

9600

Write down the address for each thermostat.

This number must be set the same at each thermostat.