APC AP9608 User Manual

Page 41

Advertising
background image

37

Press

ENTER

at the > prompt on the Measure-

UPS

screen to display fresh

readings.

MEASURE-UPS INFO

Item

Description

TEMP

Curren t ambient temperature of each attached probe, in
degrees Celsius.

Lo Limit

(Temp)

Setting for the low temperature Measure-UPS alarm.
Choose from 9.94 (the default), 14.02, 18.10, and 4.08
degrees Celsius.

Hi Limit

(Temp)

Setting for the high temperature Measure-UPS alarm.
Choose from 32.13 (the default), 45.90, 54.06, and
23.97 degrees Celsius.

HUMIDITY

Current percentage of relative humidity of each probe.

Lo Limit

(Humidity)

Setting for the low humidity Measure-UPS alarm.
Choose from 20.1 (the default), 30.2 , 40.3, and 10.0
percent relative humidity.

Hi Limit

(Humidity)

Setting for the high humidity Measure-UPS alarm.
Choose from 80.0 (the default), 84.5 , 90.1, and 70.0
percent relative humidity.

F/W

Firmware revision number of Measure-UPS.

Current Alarms

Status display of current Measure-UPS alarms, which
can include Lo Temp, High Temp, Lo RH, Hi RH, and
the four contact closures. The earlier sample screen
shows Hi Temp and Lo RH because the reported values
for these items exceed their respective alarm limits.