Adeh-75 electric models only, Adeh-170 electric models only, Grounding – American Dryer Corp. ADH-170 User Manual
Page 22: Adeh-120 electric models only, Available upon request. contact the factory, 60 kw, 72 kw, 6 kw

22
American Dryer Corp.
113247 - 3
ADEH-75 Electric Models Only
All electrically heated dryers must be connected to the electric
service shown on the dryer’s data label. The connecting
wires must be properly sized to handle the rated current.
* Customer must contact factory to special order 3-wire systems.
8/15/07
ADEH-170 Electric Models Only
Available upon request. Contact the factory.
Grounding
A ground (earth) connection must be provided and installed
in accordance with state and local codes. In the absence of
these codes, grounding must conform to applicable
requirements of the National Electrical Code ANSI/NFPA NO.
70-LATEST EDITION, or in Canada, the installation must
conform to applicable Canada Standards: Canadian Electrical
Codes Parts 1 & 2 CSA C22.1-1990 or LATEST EDITION.
The ground connection may be to a proven earth ground at
the location service panel.
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When
ordering, specify exact voltage.
When fuses are used they must be dual element, time delay,
current limiting, class RK1 or RK5 ONLY. Calculate/determine
correct fuse value, by applying either local and/or National
Electrical Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY.
For others, calculate/verify correct breaker size according
to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz
50 Hz
60 kW
380
3ш
4*
—
100
125
416
3ш
4*
—
91
125
480
3ш
3
80
—
100
600
3ш
3
64
—
80
72 kW
208
3ш
3
214
—
300
240
3ш
3
188
—
250
230
3ш
3
—
198
250
380
3ш
3
118
—
150
380
3ш
4*
—
118
150
400
3ш
4*
—
113
150
416
3ш
4*
—
108
150
460
3ш
3
98
—
125
480
3ш
3
94
—
125
575
3ш
3
78
—
100
75.6 kW
440
3ø
3
102
—
150
* Customer must contact factory to special order 3-wire systems.
8/15/07
ADEH-120 Electric Models Only
All electrically heated dryers must be connected to the electric
service shown on the dryer’s data label. The connecting
wires must be properly sized to handle the rated current.
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When
ordering, specify exact voltage.
When fuses are used they must be dual element, time delay,
current limiting, class RK1 or RK5 ONLY. Calculate/determine
correct fuse value, by applying either local and/or National
Electrical Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY.
For others, calculate/verify correct breaker size according
to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz
50 Hz
30 kW
208
3ш
3
91
—
125
230
3ш
3
—
83
125
240
3ш
3
79
—
100
380
3ш
3
48
—
60
380
3ш
4*
—
54
70
400
3ш
4*
—
51
70
416
3ш
4*
—
50
70
460
3ш
3
40
—
50
480
3ш
3
39
—
50
575
3ш
3
33
—
50
36 kW
208
3ш
3
108
—
150
230
3ш
3
—
98
125
240
3ш
3
94
—
125
380
3ш
3
58
—
80
380
3ш
4*
—
63
80
400
3ш
4*
—
60
80
416
3ш
4*
—
58
80
460
3ш
3
48
—
60
480
3ш
3
46
—
60