ADEH-75 Electric Models Only

All electrically heated dryers must be connected to the electric
service shown on the dryer’s data label. The connecting
wires must be properly sized to handle the rated current.

* Customer must contact factory to special order 3-wire systems.

8/15/07

ADEH-170 Electric Models Only

Available upon request. Contact the factory.

Grounding

A ground (earth) connection must be provided and installed
in accordance with state and local codes. In the absence of
these codes, grounding must conform to applicable
requirements of the National Electrical Code ANSI/NFPA NO.
70-LATEST EDITION, or in Canada, the installation must
conform to applicable Canada Standards: Canadian Electrical
Codes Parts 1 & 2 CSA C22.1-1990 or LATEST EDITION.
The ground connection may be to a proven earth ground at
the location service panel.

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT:

NOTES: A.

B.


C.

208 VAC AND 230/240 VAC ARE NOT THE SAME. When
ordering, specify exact voltage.

When fuses are used they must be dual element, time delay,

current limiting, class RK1 or RK5 ONLY. Calculate/determine
correct fuse value, by applying either local and/or National
Electrical Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY.
For others, calculate/verify correct breaker size according

to appliance amp draw rating and type of breaker used.

Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

CIRCUIT

BREAKER

60 Hz

50 Hz

60 kW

380

4*

100

125

416

4*

91

125

480

3

80

100

600

3

64

80

72 kW

208

3

214

300

240

3

188

250

230

3

198

250

380

3

118

150

380

4*

118

150

400

4*

113

150

416

4*

108

150

460

3

98

125

480

3

94

125

575

3

78

100

75.6 kW

440

3

102

150

* Customer must contact factory to special order 3-wire systems.

8/15/07

ADEH-120 Electric Models Only

All electrically heated dryers must be connected to the electric
service shown on the dryer’s data label. The connecting
wires must be properly sized to handle the rated current.

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT:

NOTES: A.

B.


C.

208 VAC AND 230/240 VAC ARE NOT THE SAME. When
ordering, specify exact voltage.

When fuses are used they must be dual element, time delay,

current limiting, class RK1 or RK5 ONLY. Calculate/determine
correct fuse value, by applying either local and/or National
Electrical Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY.
For others, calculate/verify correct breaker size according

to appliance amp draw rating and type of breaker used.

Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

CIRCUIT

BREAKER

60 Hz

50 Hz

30 kW

208

3

91

125

230

3

83

125

240

3

79

100

380

3

48

60

380

4*

54

70

400

4*

51

70

416

4*

50

70

460

3

40

50

480

3

39

50

575

3

33

50

36 kW

208

3

108

150

230

3

98

125

240

3

94

125

380

3

58

80

380

4*

63

80

400

4*

60

80

416

4*

58

80

460

3

48

60

480

3

46

60