Chapter 5: CPS Appliance Commands 69

SPC Command

The SPC command changes settings for an SPC device and its sockets.

NOTE: This command configures the port for use with the DSView software. For standalone use of the SPC
device, this command should not be used, and the CPS port to which the SPC is attached should be configured
as TD=Console.

Access right: SCON or PCON
Access level: ADMIN or APPLIANCEADMIN

Syntax

SPC <port>|ALL [MINLOAD=<amps>] [MAXLOAD=<amps>] [SOCKET <socket>|ALL]
[WAKE=ON|OFF] [ONMIN=<time>] [OFFmin=<time>]

Level

User’s access level. If a level was not configured, access rights determine the level:
Users with SCON access => APPLIANCEADMIN.
Users with USER or PCON but not SCON => ADMIN.
Otherwise, USER level is assigned.

Access

User’s access rights and preemption level.

Table 5.34: Show User All Command Display Fields (Continued)

Field

Contents

Table 5.35: SPC Command Parameters

Parameter

Description

<port>

Port number in range 1-8 for a CPS810 appliance or 1-16 for a CPS1610 appliance.

ALL

Indicates that the settings that follow should be applied to all ports configured
as SPC.

MINLOAD=<amps>

Minimum load in amperes in the range 0-30. A 0 value indicates no minimum load.
Default = 0

MAXLOAD=<amps>

Maximum load in amperes in the range 0-30. A 0 value indicates no maximum load.
Default = 0

SOCKET <socket>|ALL

Either a socket number on the SPC or All, which indicates that the settings that
follow should be applied to all sockets on the SPC.

WAKE=ON|OFF

State that the socket will enter when the SPC is powered up.
Default = ON