Installation and Safety Guide

15

PWR05

DC

PWR05 DC

Power supply specifications:

functional range 40 to 60 V, 48 V nominal

supports either positive grounded or negative grounded operation

a 30 Amp certified/listed circuit breaker is required for circuit protection

Supply cable specifications:

tray cable should be UL listed Type TC tray cable (or equivalent)

three-core cable is required

minimum core size: 3.3 mm

2

(12 AWG) high strand count copper wire

minimum cable rating: 600 V, 90 degrees C

Warning When mounting one or two AT-PWR05 DC PSUs to a grounded rack,
ensure that the ground level of the rack and the DC power connector are the
same.

1.

Ensure that the circuit breaker for the supply circuit and the Run/Standby
switch on the PSU are off (slide to position O).

2.

Plug the DC power cord into the power inlet on the PSU.

3.

Connect the supply cable wires to the circuit breaker and switch the circuit
breaker ON.

4.

Turn on the PSU by sliding in the Run/Standby switch to position 1.

DC

IN

LED

RUN/STANDBY

SWITCH

CAPTIVE

SCREW

DC

OUT

LED

FAULT

LED

N/C

GREEN

( GND )

RED
( + )

BLACK

( - )