Adg-530d (gas), Electrical service specifications (per pocket) – American Dryer Corp. ADG-530D II User Manual

Page 29

Advertising
background image

25

3. Grounding

A ground (earth) connection must be provided and installed in accordance with state and local codes. In
the absence of these codes, grounding must conform to applicable requirements of the National Electrical
Code ANSI/NFPA NO. 70-LATEST EDITION, or in Canada, the installation must conform to applicable
Canada Standards: Canadian Electrical Codes Parts 1 & 2 CSA C22.1-1990 or LATEST EDITION. The
ground connection may be to a proven earth ground at the location service panel.

For added personal safety, when possible, it is suggested that a separate ground wire (sized per local codes)
be connected from the ground connection of the dryer to a cold water pipe. DO NOT ground to a gas
pipe or hot water pipe.
The grounded cold water pipe must have metal to metal connections ALL the
way to the electrical ground. If there are any nonmetallic interruptions, such as, a meter, pump, plastic, or
other insulating connectors, they must be jumped out with no. 4 wire and securely clamped to bare metal
at both ends.

IMPORTANT: For personal safety and proper operation, the dryer must be grounded.

4. Electrical Service Specifications (per pocket)

IMPORTANT: The dryer must be connected to the electrical supply shown on the data label located

behind the left coin control panel on the right wall (refer to Section IX in this manual).

WARNING: Any damage done to the dryer components due to improper voltage application or

connections will automatically VOID THE WARRANTY.

5. Electrical Specifications

NOTE: ADC reserves the right to make changes in specifications at any time without notice or

obligation.

0 4 3 0 0 3

ADG-530D (Gas)

ELECTRICAL SERVICE SPECIFICATIONS (PER POCKET)

IMPORTANT: 208 VAC and 230 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

NOTES: A. When fuses are used they must be dual element, time delay, current limiting, class RK1 or

RK5 ONLY. Calculate/determine correct fuse value, by applying either local and/or

National Electrical Codes to listed appliance amp draw data.

B. Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY. For others,

calculate/verify correct breaker size according to appliance amp draw rating and type of

breaker used.

SERVICE

VOLTAGE PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

MINIMUM

WIRE SIZE

FUSING

CIRCUIT

BREAKER

Dual Element

Time Delay

120

2

9.7

*

15

15

208

2

5.8

*

15

15

230

2

5.4

*

15

15

* AWG Stranded Wire Type...size wire as per National Electrical Code or local codes.