2. Electrical Service Specifications

a. Gas and Steam Models ONLY

IMPORTANT: Figures shown are for Non-Reversing Models ONLY. For reversing models contact

the factory.

IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is

affixed to the back side of the upper/top control door. In the case of 208 VAC or
230/240 VAC, the supply voltage must match the electric service specifications of
the data label exactly.

IMPORTANT: The wire size must be properly sized to handle the related current.

WARNING: 208 VAC and 230/240 VAC ARE NOT THE SAME. Any damage done to dryer

components due to improper voltage connections will automatically VOID THE
WARRANTY.

NOTE: ADC reserves the right to make changes in specifications at any time, without notice or

obligation.

EURO-35 (G

AS

)

EURO-35

(S

TEAM

)

IMPORTANT: 208 VAC and 230/240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

NOTES:

A. Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5 ONLY.

B. Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker

size according to appliance amp draw rating and type of breaker used.

C. Circuit breakers for 3Ø dryers must be 3-pole type.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

MINIMUM

WIRE SIZE*

FUSING

Dual Element

Time Delay

CIRCUIT

BREAKER

120

2

13

#10

20

20

208

2

8

#14

12

15

208

3/4

5

#14

8

15

230

2

7

#14

12

15

230

3/4

5

#14

8

15

240

2

7

#14

12

15

380/400

3/4

3

#14

5

15

416

3/4

3

#14

5

15

460

3/4

3

#14

5

15

* AWG Stranded Wire ... for individual lengths less than 100 feet (30.48 m).