TRACER CH532 offers customer the
possibility to use inputs or outputs
in order to:
- use an external water setpoint

reset using an analog input
(refer to figure 3)

- use an auxiliary setpoint
- connect a remote on/off of the unit

or a circuit

- reset faults
- connect a remote Cooling/Heating

switch

- return a circuit fault

Note: External water setpoint
Based on a external signal input, it
will be possible to offset the active
setpoint from 0°C to 20°C. This
function can be used in conjunction
with the automatic setpoint reset
function.

Figure 3

1. Leaving water temperature setpoint
2. Minimum value
3. Maximum value
4. Reset = 20°C
5. Active setpoint

Table 3: Customer Inputs and output summary list

TRACER CH532 Medium

TRACER CH532 Large

Single circuit units

Dual circuit units

AI

External water setpoint reset (option)

B8: 0..10V-0..20mA

DI

Auxiliary setpoint On/Off

ID8: 24Vac

DI

Circuit 1 On/Off (or Unit On/Off
for single circuit units)

ID13H: 230Vac

DI

Circuit 2 On/Off

-

ID16H: 230Vac

DI

Faults external reset

ID6: 24Vac

DI

Cooling/Heating mode switch

ID7: 24Vac

DO

Circuit 1 fault

NO9: NO-230Vac

DO

Circuit 2 fault

-

NO11: NO-230Vac

DO

Unit status or additional
heating demand

NO10: NO-230Vac

Legend:
AI: Analog Input
DI: Digital Input
DO: Digital Output

5

1

4

2

3

Ambient

temperature

W

ater setpoint

Hardware architecture