Event mask example, Event-related menus and options, How to configure individual events continued – APC AP9211 User Manual

Page 39

Advertising
background image

MasterSwitch Power Distribution Unit User’s Guide

35

Event-Related Menus and Options

How to Configure Individual Events

continued

Event mask

example

You enter the hexadecimal code

3B0800

as an event mask.

The event mask configures the following bit settings:

0011 1011 0000 1000 0000 0000

The event is configured as follows:

The severity level is severe.

The event will be logged.

Traps generated by the event will be sent to trap receivers

1

and

2

.

When the event occurs, e-mail will be sent to recipient

3

only.