The installation diagram below has a solid curb cap duct

adapter placed over the top of the curb. The welded grease
duct with recommended transition is either welded or
sealed with UL recognized fire caulk to both the curb cap
duct adapter and the bottom of the fan. A minimum of two
separate outlines of caulk is recommended at the outer
portion of the curb cap duct adapter.

Wheel-to-Inlet Clearance

The correct wheel-to-inlet clearance is critical to proper

fan performance. This clearance should be verified before
initial start-up since rough handling during shipment could
cause a shift in fan components. Refer to wheel/inlet draw-
ing for correct overlap.

Adjust the overlap by loosening the wheel hub and mov-

ing the wheel along the shaft to obtain the correct value.

A uniform radial gap (space between the edge of the

cone and the edge of the inlet) is obtained by loosening the
inlet cone bolts and repositioning the inlet cone.

CA, CF, & CP

CAF-DW

Size

Overlap

60 - 165

3/16”

180 - 245

1/4”

270 - 300

5/16”

330 - 365

3/8”

402

7/16”

445 - 490

1/2”

540 - 730

13/16”

Size

Overlap

120

1/8”

135 - 165

5/32”

180

1/4”

195

5/32”

210

1/4”

225

5/32”

245

9/32”

270 - 445

1/4”

490

17/32”

540 - 600

27/32”

660 - 730

25/32”

Duct Installation

Efficient fan performance relies on the proper installation

of inlet and discharge ducts. Be sure your fan conforms to
the following guidelines.

Non-Ducted Inlet Clearance: If your fan has an open inlet

(no duct work), the fan must be placed 1 fan wheel
diameter away from walls and bulkheads.

Free Discharge: Avoid a free discharge into the plenum.
This will result in lost efficiency because it doesn’t allow for
a static regain.

Inlet Duct Turns: For ducted inlets, allow at least 3 fan
wheel diameters between duct turns or elbows and the fan
inlet.

Discharge Duct Turns: Where possible, allow 3 duct diame-
ters between duct turns or elbows and the fan outlet. Refer
to figure above.

CP with Optional Curb Cap & Inlet Box

UL 762 / NFPA96 and local codes may dictate
additional or modifications to this installation.

Non-ducted Inlet

MIN 1 DIA

Clearance

Free Discharge

Correct

Incorrect

Correct

Incorrect

Inlet Duct Turns

MIN 3

DIA

Correct

Incorrect

Discharge Duct Turns

MIN 3

DIA