Chapter 4--wiring – Lyntec RPC User Manual
Page 11

139-0498-01.11
11
Chapter Four--Wiring
Chapter 4--Wiring
1. Install and connect all main and neutral feeds as per NEC.
2. Install and connect the Isolated Technical Ground feed from
the star ground of the isolation transformer or the tie point
from a ground rod or building steel to the Isolated Technical
Ground bar in the ITG sidecar.
3. Ensure all breakers are properly installed in the panel and
that the motorized breakers are fi rmly plugged into the
adjacent control busses.
To initially wire the RPC follow these easy steps:
Figure 4-1: Power Supply
Steps four, fi ve and six are completed at the factory. The
instructions are included as a reference only.
4. Connect the black 14 AWG wire from the Load terminal of
the Power Supply unit (Figure 4-1--located at the top of the
Isolated Technical Ground sidecar) to the 15 Amp Controller
Power breaker in the panel.
5. Connect the white 14 AWG wire from the Neutral terminal
of the Power Supply unit to the neutral bus located below
the breakers in the panel.
Panel Neutral Bus
Panel Ground Bar
Power Supply DC –
Controller Cable
Controller Cable
Power Supply DC +
N L
+ + – –
15A Breaker in Panel
Transducer Neutral
Transducer Load