Setup process – Pulsafeeder MPC Vector User Manual

Page 46

Advertising
background image

40

Setup Process

1. Navigate to the

CALIBRATION

menu, and scroll to the

MOTOR PARAM

option. The starting

display will be:

C A L I B R A T I O N
M O T O R P A R A M

2. Press the ENTER key

8 5

< 1 8 0 0 >

3. Use UP and DOWN arrows to adjust value as required, then press the ENTER key

8 6

< 1 . 2 >

4. Use UP and DOWN arrows to adjust value as required, then press the ENTER key

8 7

< 2 3 0 >

5. Use UP and DOWN arrows to adjust value as required, then press the ENTER key

8 8

< 6 0 >

6. Use UP and DOWN arrows to adjust value as required, then press the ENTER key

9 1

< 0 . 8 0 >

7. Use UP and DOWN arrows to adjust value as required, then press the ENTER key

8 1

E N T E R T O S T A R T

8. Press the ENTER key

C A L I B R A T I N G

9. The last screen will show

M O T O R P A R A M

c a l i b r a t e d

10. Upon completion of the routine, remove power from the MPC VECTOR controller for one minute,

and then re-apply power to complete the process.

After all of the Parameters have been entered, the drive needs to perform an auto-calibration routine
(Parameter 81). This calibration routine will take several seconds to complete. The user may use the Menu
Key to back up and/or out of the calibration any time prior to the auto calibration. The motor, and therefore
the pump, will not run during this auto-calibration procedure.