Safety Precautions

•

All devices have to be supplied by a Class 2 power supply.

Warning:
Do not disconnect equipment unless power has been removed or the area is
known to be non-hazardous

•

For Canada also AVERTISSEMENT – AVANT DE DECONNECTER
L’EQUIPEMENT, COUPER LE COURANT OUS’ASSURER QUE
L‘EMPLACEMENT EST DESIGNE NON DANGEREUX.

Warning:
Only UL and cUL approved expansion units are allowed to be connected to
the port designated “EXPANSION”. At the moment there are no such units
evaluated or allowed.

Warning:
Do not replace expansion unit unless power has been switched off or the area
is known to be non-hazardous.

•

This product contains a battery; this must only be changed in an area known
to be non-hazardous.

•

Replace the battery with a BR 2032 battery. Use of another type of battery
may present a risk of fire or explosion.

Warning:
Battery may explode if mistreated. Do not recharge, disassemble or dispose
of in fire.

•

For use on a flat surface of a type 4X enclosure indoor use only.

•

Use 75 degree conductors only

•

Use copper conductors only

•

To make wiring connections to the power supply connector, follow the table
with cable and torque specifications below:

Terminal Block No.

Wire Size AWG

TQ Lb.In.

X1/X100 Phoenix connectors

AWG 30–12

5–7

X1/X100 Anytek connectors

AWG 24–12

3.5

•

These devices are Class 2 supplied programmable controllers (industrial PCs)
for the use in industrial control equipment and are intended to be (front)
panel mounted (Type 1 and 4x for indoor use only).

Beijer Electronics, MAEN016F

5

Advertising