Shutoff Valve

Circulating Pumps

Stem Thermometer

Supply to System

Return from System

Bypass A

S

R

Cold Water Feed



Drain Cock

Circulating Pumps

Adjust the two manual valves to maintain 160 degree F or more in the boiler while holding the supply water
temperature at the stem thermometer at 140 degree F or whatever minimum temperature system requires.

Figure 20.

NOTE

Bypass A shown in figure 20. above should not exceed 12 inches in length. If it
is not practical to maintain a 12 inch length or less then increase the pipe size of
the bypass by one size.







4.

LARGE WATER CONTENT SYSTEMS------
Such systems as converted gravity systems, old systems with cast iron radiators, and
also newer systems that employ outdoor reset control present a potential problem with
low return water temperatures and condensation. The boiler must be protected from
condensation in such cases by using a by-pass as shown in Figure 21.