TROUBLESHOOTING

Problem:
No Reading

•

Check that you have the correct supply
voltage at the power terminal blocks.

•

Check that wiring configurations and all
DIP switch settings are as in Figures #1,
#2 and #7
.

•

Verify that the terminal screws are all
connected tightly and that all of the wires
are firmly in place.

Erratic Readings

•

Verify that all of the wires are terminated
properly.

•

Make sure that there is no condensation
on the board.

•

Check that the input power is clean. In
areas of high RF interference or noise,
shielded cable may be necessary to
stabilize signal.

Inaccurate Readings

•

If you suspect that the transmitter is not
reading within the specified tolerance,
please contact the factory for further
assistance.

4-20m A Output: 250 Ohm Load 22 - 40
VDC / 22 - 28 VAC

RH M easurement Range

0 - 100% RH

4-20m A Output: 500 Ohm Load 24 - 40
VDC / 24 - 28 VAC (500 Ohm Load Max)

RH Accuracy @ 77

o

F (25

o

C)

± 1% over 20% span (between 20 to 90%)
± 2% , 3% , or 5% from 10 to 95%

Repeatability

0.5% RH

Operating Humidity Environment 0 to 95% RH

Supply Current

24mA M ax

Operating Temp. E nvironment

32 to 122

°F (0 to 50°C)

2-Wire, 4-20 mA

Storage Temp. Range

-40 to 160

°F (-40 to 71°C)

3-Wire, 4-20mA

Supply Voltage

RH Output

PRODUCT SPECIFICATIONS