Bell & Gossett 10-001-278 XLS Integrated Pump Controller User Manual
Page 20

20
will still operate during this process, but the HMI will not
show pressure/flow etc., remote connection will be lost
etc. However there will be no loss of pump operation.
Typical settings for Modbus TCP are as follows:
Page Modbus - Link
Serial Encapsulation
TCP/IP
Connection
TCP/IP
Station ID
1
Protocol
RTU
Page
Modbus - Modem
Configuration
Modem Identifier
Auto Detect
2
Phone Number
<As
Required >
Page Modbus - Modem Options
Enable incoming calls
No
Auto Connect Enable
Yes
Auto Connect Retry
Interval (s)
120
Disconnect if call idle more
than...
1
Auto-Disconnect time (s)
120
Page Modbus - Com Port
Com Port
COM2
Baud
9600
Data Bits
8
Stop Bits
1
Parity
None
Page Modbus - TCP and UDP
IP Address
192.168.1.1
5
Port #
502
Server Mode
Yes
Page Modbus - Advanced - A
Use Transaction ID
Yes
Word Type
Unsigned
Protocol-Retries
0
TX Buffer
512
RX Buffer
512
Page Modbus - Advanced - B
TimeOut-Start
1000
TimeOut-End
0
TimeOut-Interval Between
Char
500
TimeOut-Wait CTS
100
Page Modbus - Advanced - C
Control RTS
No
Verify CTS
No
Disable DTR
No
Enable IR
No
Table 1: Modbus TCP Settings