10

Multi-Position Air Handler with Hydronic Heat with X13 Motor

HWCGxxX0A

Heat Controller

Table 2. Volume Sizing Guide

CFM

Min Water Heater

600-800

40 gal

1000-1200

50 gal

1400-1600

2x40 gallons piped together

High input 50 gallons (63-75k Btu)

72-75gallons

2000

105k Btu

Table 2. Volume Sizing Guide

b. To determine water heater BTU INPUT (assumes a

water heater recovery efficiency of 76%): For mild

climates: BTU INPUT=structure’s heat loss x 1.51. For

colder climates: BTU INPUT=structure's heat loss x

1.58.

3) Pump Replacement

a. Disconnect electrical power to the unit before

servicing.

b. Remove access door to reveal pump. Close supply

valve ("A") and return valve ("B"). Open the air bleed

valve to de-pressurize the system and drain water.

c. Remove the metal pump housing by loosening the

four screws on the pump. DO NOT UN-SOLDER PUMP.

d. Replace the new pump housing assembly and

reconnect components to the pump. Before assembling,

make sure that the runner on the o-ring is in place on the

pump housing.

e. Purge the system of the air as described earlier and

re-connect the electrical power.

Common Problems and Solutions

1) Noisy Pump

System may not be totally purged of air. Purge the

system again as described in the start up section above.

2) T&P valve on water heater weeps

This nomally occurs when a backflow preventer has been

installed in the cold water supply line to the water heater. An

expansion tank may be necessary to correct this problem.

Please contact a qualified plumbing professional for assitance.

3) Hot water is circulating through the water coil during

cooling cycle

The check valve may be stuck open and allowing hot water to

circulate through the coil.

4) Little or no heat from water coil

a. Purge the system

b. The inlet connections may be reversed at the fan coil

c. Water heater thermostat is not set at proper temp

d. Water heater thermostat is not caliberated

e. Dip tube in the water heater maynot be installed

correctly or could be restricted.

f. Look for restrictions in heating system from water

heater to fan coil. Some water heaters are supplied with

check valves. Remove any extra check valves except for

the one supplied with the fan coil

g. The air handler is undersized for space being heated

h. Water heater is undersized

Note: All units installed in Massachusetts are required to

be in compliance with CMR 248 Massachusetts State

Plumbing Code and/or Massachusetts Fuel Gas Code.

These codes require the use of an optional pump timer

to circulate the hydronic loop independent of the

thermostat.