Comfort-Aire HBH Series 1/2 to 5 Ton User Manual

Page 39

Advertising
background image

Heat Controller, Inc.

HBH/V COMPACT

IOM Instructions

Preventive Maintenance

Water Coil Maintenance

(Direct ground water applications only)

If the system is installed in an area with a known high

mineral content (125 P.P.M. or greater) in the water, it is

best to establish a periodic maintenance schedule with

the owner so the coil can be checked regularly. Consult

the well water applications section of this manual for

a more detailed water coil material selection. Should

periodic coil cleaning be necessary, use standard coil

cleaning procedures, which are compatible with the heat

exchanger material and copper water lines. Generally,

the more water flowing through the unit, the less chance

for scaling. Therefore, 1.5 gpm per ton [1.6 l/m per kW]

is recommended as a minimum flow. Minimum flow rate

for entering water temperatures below 50°F [10°C] is 2.0

gpm per ton [2.2 l/m per kW].

Water Coil Maintenance

(All other water loop applications)

Generally water coil maintenance is not needed for

closed loop systems. However, if the piping is known to

have high dirt or debris content, it is best to establish a

periodic maintenance schedule with the owner so the

water coil can be checked regularly. Dirty installations are

typically the result of deterioration of iron or galvanized

piping or components in the system. Open cooling

towers requiring heavy chemical treatment and mineral

buildup through water use can also contribute to higher

maintenance. Should periodic coil cleaning be necessary,

use standard coil cleaning procedures, which are

compatible with both the heat exchanger material and

copper water lines. Generally, the more water flowing

through the unit, the less chance for scaling. However,

flow rates over 3 gpm per ton (3.9 l/m per kW) can

produce water (or debris) velocities that can erode the

heat exchanger wall and ultimately produce leaks.

Filters

Filters must be clean to obtain maximum performance.

Filters should be inspected every month under normal

operating conditions and be replaced when necessary.

Units should never be operated without a filter.

Washable, high efficiency, electrostatic filters, when dirty,

can exhibit a very high pressure drop for the fan motor

and reduce air flow, resulting in poor performance. It is

especially important to provide consistent washing of

these filters (in the opposite direction of the normal air

flow) once per month using a high pressure wash similar

to those found at self-serve car washes.

Condensate Drain

In areas where airborne bacteria may produce a “slimy”

substance in the drain pan, it may be necessary to treat

the drain pan chemically with an algaecide approximately

every three months to minimize the problem. The

condensate pan may also need to be cleaned periodically

to insure indoor air quality. The condensate drain can

pick up lint and dirt, especially with dirty filters. Inspect

the drain twice a year to avoid the possibility of plugging

and eventual overflow.

Compressor

Conduct annual amperage checks to insure that amp

draw is no more than 10% greater than indicated on the

serial plate data.

Fan Motors

All units have lubricated fan motors. Fan motors should

never be lubricated unless obvious, dry operation

is suspected. Periodic maintenance oiling is not

recommended, as it will result in dirt accumulating in the

excess oil and cause eventual motor failure. Conduct

annual dry operation check and amperage check to

insure amp draw is no more than 10% greater than

indicated on serial plate data.

Air Coil

The air coil must be cleaned to obtain maximum

performance. Check once a year under normal operating

conditions and, if dirty, brush or vacuum clean. Care must

be taken not to damage the aluminum fins while cleaning.

CAUTION: Fin edges are sharp.

Cabinet

Do not allow water to stay in contact with the cabinet for

long periods of time to prevent corrosion of the cabinet

sheet metal. Generally, vertical cabinets are set up from

the floor a few inches [7 - 8 cm] to prevent water from

entering the cabinet. The cabinet can be cleaned using a

mild detergent.

Refrigerant System

To maintain sealed circuit integrity, do not install service

gauges unless unit operation appears abnormal.

Reference the operating charts for pressures and

temperatures. Verify that air and water flow rates are at

proper levels before servicing the refrigerant circuit.

Advertising
This manual is related to the following products: